![Xtender XTS 900-12 User Manual Download Page 54](http://html1.mh-extra.com/html/xtender/xts-900-12/xts-900-12_user-manual_3704848054.webp)
Studer Innotec SA
Xtender
User manual
V4.6.0
54
21
TECHNICAL DATA
Inverter model
XTS 900-12
XTS 1200-24
XTS 1400-48
XTM 1500-12
XTM 2000-12
XTM 2400-24
XTM 2600-48
XTM 3500-24
XTM 4000-48
XTH 3000-12
XTH 5000-24
XTH 6000-48
XTH 8000-48
Nominal battery voltage
12Vdc
24Vdc
48Vdc
12Vdc
24Vdc
48Vdc
24Vdc
48Vdc
12Vdc
24Vdc
48Vdc
Input voltage range
9.5-17Vdc
19-34Vdc
38-68Vdc
9.5-17Vdc
19-34Vdc
38 - 68Vdc
19-34Vdc
38-68Vdc
9.5-17Vdc
19-34Vdc
38-68Vdc
Continuous power @ 25°C
650**/500VA
800**/650VA 900**/750VA
1500VA
2000VA
3000VA
3500VA
2500VA
4500VA
5000VA
7000VA
Power 30 min. @ 25°C
900**/700VA
1200**/1000
VA
1400**/1200
VA
1500VA
2000VA
2400VA
2600VA
3500VA
4000VA
3000VA
5000VA
6000VA
8000VA
Power 3 sec. @25°C
2.3kVA
2.5kVA
2.8kVA
3.4kVA
4.8kVA
6kVA
6.5kVA
9kVA
10.5kVA
7.5kVA
12kVA
15kVA
21kVA
Maximum load
Up to short-circuit
Maximum asymmetric load
Up to Pcont.
* Load detection (Stand-by)
2 to 25W
Cos φ
0.1-1
Maximum efficiency.
93%
93%
93%
93%
94%
96%
94%
96%
93%
94%
96%
Consumption OFF/Stand-by/ON
1.1W/1.4W/7W 1.2W/1.5W/8W 1.3W/1.6W/8W 1.2W/1.4W/8
W
1.2W/1.4W/10
W
1.4W/1.6W/9W 1.8W/2W/10W 1.4W/1.6W/12
W
1.8W/2.1W/14
W
1.2W/1.4W/14
W
1.4W/1.8W/18
W
1.8W/2.2W/22W 1.8W/2.4W/30W
* Output voltage
Pure sine wave 230Vac (+/- 2%) / 120Vac (1)
* Output frequency
50Hz / 60Hz(1) +/- 0.05% (crystal controlled)
Harmonic distortion
<2%
Overload and short-circuit protection
Automatic disconnection with 3 restart attempts
Overheat protection
Warning before shut-down – with automatic restart
Battery charger
* Charge characteristics
6 steps : bulk - absorption - floating - equalization - reduced floating – periodic absorption
* Maximum charging current
35A
25A
12A
70A
100A
55A
30A
90A
50A
160A
140A
100A
120A
* Temperature compensation
WithBTS-01 or BSP 500/1200
Power factor correction (PFC)
EN 61000-3-2
General data
XTS 900-12
XTS 1200-24
XTS 1400-48
XTM 1500-12
XTM 2000-12
XTM 2400-24
XTM 2600-48
XTM 3500-24
XTM 4000-48
XTH 3000-12
XTH 5000-24
XTH 6000-48
XTH 8000-48
* Input voltage range
150 to 265Vac / 50 to 140Vac(1)
Input frequency
45 to 65Hz
Input current max. (transfer relay) /
Output current max.
16Aac/20Aac
50Aac/56Aac
50Aac/80Aac
Transfer time (UPS)
<15ms
Multifunction contacts
Module ARM-02 with 2 contacts as option
Two independent switchover contacts ( potential free,16A-250 Vac / 3A-50Vdc)
Weight
8.2 kg
9kg
9.3 kg
15 kg
18.5 kg
16.2 kg
21.2 kg
22.9 kg
34 kg
40 kg
42 kg
46 kg
Dimension h x w x l [mm]
110x210x310 110x210x310 110x210x310
133x322x466
133x322x466
230x300x500 230x300x500
230x300x500
Protection index
IP54
IP20
Conformity
Directive EMC 2004/108/CE : EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, 62040-2
Low voltage directive : 2006/95/CE : EN 50178, EN 62040-1, EN 60950-1, EN 62109-1
Operating temperature range
-20 to 55°C
Relative humidity in operation
100%
95% without condensation
Ventilation
Optional cooling module ECF-01
Forced from 55°C
Acoustic level
<40dB / <45dB (without / with ventilation)
*
Adjustable value
* *
value with optional cooling fan module ECF-01
(1)
With -01 at the end of the reference (I.e. XTM3500-24-01), means 120V/60Hz. Available for all Xtender except XTH 8000-48