Studer Innotec SA
Xtender
User manual
V4.6.0
48
Access
level
Param.
N°
Denomination / description
Fact. value
2
Mod.
value
Expert
1188 Standby number of pulses
1
Expert
1189 Time delay between standby pulses
0.8 sec
Expert
1190 Battery undervoltage duration before turn off
3 min
Expert
1191 Battery undervoltage dynamic compensation
Yes
NC
4
Expert
1194 Battery adaptive low voltage (B.L.O)
No
Expert
1195 Max voltage for adaptive low voltage
12.5/25/49.9 Vdc
Expert
1198 Time delay before opening of transfer relay
8 sec
Expert
1199 Input voltage giving an opening of the transfer relay
with delay
180 Vac
Expert
1200 Input voltage giving an immediate opening of the
transfer relay (UPS)
90 Vac
Expert
1202 Operating mode (AUX 1)
Automatic
Expert
1205 Day of the week (AUX 1)
None days
Expert
1206 Start hour (AUX 1)
07:00 hh:mm
Expert
1207 End hour (AUX 1)
20:00 hh:mm
Expert
1209 Day of the week (AUX 1)
None days
Expert
1210 Start hour (AUX 1)
07:00 hh:mm
Expert
1211 End hour (AUX 1)
20:00 hh:mm
Expert
1213 Day of the week (AUX 1)
None days
Expert
1214 Start hour (AUX 1)
07:00 hh:mm
Expert
1215 End hour (AUX 1)
20:00 hh:mm
Inst.
1217 Day of the week (AUX 1)
None days
Inst.
1218 Start hour (AUX 1)
07:00 hh:mm
Inst.
1219 End hour (AUX 1)
20:00 hh:mm
Inst.
1221 Day of the week (AUX 1)
None days
Inst.
1222 Start hour (AUX 1)
07:00 hh:mm
Inst.
1223 End hour (AUX 1)
20:00 hh:mm
Expert
1225 Xtender is OFF (AUX 1)
No
Expert
1226 Battery undervoltage alarm (AUX 1)
No
Expert
1227 Battery overvoltage (AUX 1)
No
Expert
1228 Inverter or Smart- Boost overload (AUX 1)
No
Expert
1229 Overtemperature (AUX 1)
No
Expert
1231 Active charger (AUX 1)
No
Expert
1232 Active inverter (AUX 1)
No
Expert
1233 Active Smart-Boost (AUX 1)
No
Expert
1234 AC input presence but with fault (AUX 1)
No
Expert
1235 AC input presence (AUX 1)
No
Expert
1236 Transfer relay ON (AUX 1)
No
Expert
1237 AC out presence (AUX 1)
No
Expert
1238 Bulk charge phase (AUX 1)
No
Expert
1239 Absorption phase (AUX 1)
No
Expert
1240 Equalization phase (AUX 1)
No
Expert
1242 Floating (AUX 1)
No
Expert
1243 Reduced floating (AUX 1)
No
Expert
1244 Periodic absorption (AUX 1)
No
Expert
1246 Battery voltage 1 activate (AUX 1)
Yes
Expert
1247 Battery voltage 1 (AUX 1)
11.7/23.4/46.8 Vdc
Expert
1248 Delay 1 (AUX 1)
1 min
Expert
1249 Battery voltage 2 activate (AUX 1)
Yes
Expert
1250 Battery voltage 2 (AUX 1)
11.9/23.9/47.8 Vdc
Expert
1251 Delay 2 (AUX 1)
10 min
Expert
1252 Battery voltage 3 activate (AUX 1)
Yes
Expert
1253 Battery voltage 3 (AUX 1)
12.1/24.2/48.5 Vdc
Expert
1254 Delay 3 (AUX 1)
60 min
Expert
1255 Battery voltage to deactivate (AUX 1)
13.5/27/54 Vdc