29
DEC for reverse jog. Press STATUS/ESC to exit.
4 statuses when jogging:
Status
Display
Status
Display
Idle
Forward
Enable
Reverse
(
2
)
test run
(
F1-01
)
Make sure the motor doesn’t connect to the machine before test running
!
Please enter test run if servo connects to non-original encoder line and power line.
Set F1-01 to 1, keep press ENTER to go to test run.
The display will show the following when test running.
If all the wires are connected correctly, the motor will run forward (direction is
counterclockwise) in 5 seconds. The motor will shake if the wiring is not correct.
Even worse, the drive will alarm. Please cut the power at this time and check the
wiring.
Press STATUS/ESC to exit.
(
3
)
current detection offset auto-tune
Please use current detection offset auto-tune when servo finishes updating or motor
is not running smoothly after long time.
Choose F1-02 to enter current detection offset auto-tune, it will show rEF.
Press ENTER to run this function, it will show rEF and blink.
It will show done in 5 second when auto-tune is successful.
Press STATUS/ESC to exit.
(
4
)
speed command offset auto-tune
Choose F1-03 to enter this function. It will show rEF_o.