PRINTER SPECIFICATIONS AND REQUIREMENTS
6-2
XEROX DOCUPRINT 96/4635/180 IPS INSTALLATION PLANNING GUIDE
Outlet configurations
This section discusses specifications for system outlets and the
required wall outlet configurations for the USA / Canada and
internationally.
Note:
All power outlets must be dedicated to this equipment. When
determining the electrical connections for your printer, make sure
that:
•
Each power cord has a separate circuit
•
The printer power cord configurations match your receptacle
•
Your electrical outlets are within the required specifications.
50 Hz systems: Ensure that power connections are per local codes/
regulations.
Printer outlet voltages—60 Hz
The following table shows the voltages for the outlets on your printing
system. All power outlets must have a dedicated circuit for each
system equipment piece. Make sure each power cord has a separate
circuit.
Table 6-2.
Printer (60 Hz) voltage requirements at power outlet
Service outlet
configuration
Measurement of wiring
Nominal
Range
4 Wire
Line 1 to neutral
120 V RMS
107-127 V RMS
4 Wire
Line 2 to neutral
120 V RMS
107-127 V RMS
4 Wire
Neutral to ground
0
0-10 V RMS
4 Wire
Line 1 to line 2
208 V RMS
182-220 V RMS
4 Wire
Line 1 to line 2
240 V RMS
210-254 V RMS
Summary of Contents for DocuPrint 180 IPS Series
Page 1: ...Xerox DocuPrint 96 4635 180 IPS Installation Planning Guide Version 7 1 XJXVW 2000 721P88230...
Page 10: ...TABLE OF CONTENTS x XEROX DOCUPRINT 96 4635 180 IPS INSTALLATION PLANNING GUIDE...
Page 48: ...PREPARING FOR INSTALLATION 4 8 XEROX DOCUPRINT 96 4635 180 IPS INSTALLATION PLANNING GUIDE...
Page 98: ......
Page 128: ...SUPPLIES A 24 XEROX DOCUPRINT 96 4635 180 IPS INSTALLATION PLANNING GUIDE...
Page 194: ...GLOSSARY GLOSSARY 16 XEROX DOCUPRINT 96 4635 180 IPS INSTALLATION PLANNING GUIDE...
Page 200: ...INDEX INDEX 6 XEROX DOCUPRINT 96 4635 180 IPS INSTALLATION PLANNING GUIDE...