RC7 & RC7GS Remote Controls
Inverter/Charger Error Messages
Error messages display when a fault is detected with either the inverter or
charger. The red Error LED lights, and the buzzer sounds. Error messages for
the inverter/charger display the error condition as well as a suggested remedy.
1.
Over Temperature
The “Otemp / Less Load” System Status message indicates the inverter/
charger transformer and power components have exceeded a safe operating
temperature. Reduce the load on the inverter. When the unit has cooled, it will
automatically reset and resume operation. If this condition occurs often, make
sure the inverter is in a cool location, has adequate ventilation and the cooling
fan is operational.
Figure 47
Error Display–Over Temperature
2.
Overload
The “Overload” System Status message is displayed when the load on the
inverter/charger exceeds the maximum power rating of the unit. Reduce the load
and restart the inverter/charger by pressing the ON/OFF push-button on the
RC7 twice.
Figure 48
Error Display–Overload
25
System Status:
Otemp / Less Load
Inverter
Charge
Batt. Full
Error
822-4A-001
Error Condition
Remedy
Error LED ON
Buzzer Sounds
System Status:
Overload
Inverter
Charge
Batt. Full
Error
822-4A-001
Error LED ON
Error Condition
Buzzer Sounds
3.0 OPERATION
NOTE: Press any arrow push-button to cancel the buzzer.
NOTE: Press any arrow push-button to cancel the buzzer.