RC7 & RC7GS Remote Controls
NOTE: Press any arrow push-button to cancel the buzzer.
NOTE: If the genset is manually started from the RC7GS remote, a manual
override is initiated and it will not shut down automatically. “Man Stop Only!!”
(Figure 39) will be displayed in the LCD. Shut down the genset manually as
previously described.
NOTE: The Gen Quiet Fault error is not actually a system error or fault but rather
an alert that the system has reached the selected auto-start parameter during
the quiet time selected.
Figure 38
Gen Quiet Fault Error Message
Genset Status:
Man Stop Only!!
Figure 39
Genset Manual Stop Only Display
3.0 OPERATION
21
The Gen Quiet Fault error is automatically reset at the end of the quiet time
period if no other action is taken.
Figure 40
Low AC Input V Error Message
3.
Low AC Input V
The Low AC Input V Fault error indicates the input AC voltage is below
45 V AC (B+ is present–Power Tech generators only). The red error LED is ON
and the buzzer sounds. When the AC voltage is above 45 V AC, this error
message will disappear.
Genset Status:
Gen Quiet Fault
Inverter
Charge
Batt. Full
Error
822-4A-001
Red Error LED Lights and Error Message Appears in the LCD
Display and buzzer sounds.
Buzzer Sounds
Genset Status:
Low AC Input V
Red Error LED Lights and Error Message Appears
in the LCD Display and buzzer sounds.
Buzzer Sounds
Inverter
Charge
Batt. Full
Error
822-4A-001
NOTE: Press any arrow push-button to cancel the buzzer.