Configuration
3–36
975-0082-01-01
User Settings
Use this table to record any customized Auto Gen Start settings for future
reference.
Setting
Values
Default
User Setting
“QT Begin”
12:00AM–11:59PM (12-hour clock)
00:00–23:59 (24-hour clock)
9:00PM (12-hour clock)
21:00 (24-hour clock)
“QT End”
12:00AM–11:59PM (12-hour clock)
00:00–23:59 (24-hour clock)
8:00AM (12-hour clock)
8:00 (24-hour clock)
“Gen Type”
Type 1 to Type 13
Type 2
“StartV:30sec”
Off, 4.0V–60.0V
11.3V
“StartV:15min”
Off, 4.0V–60.0V
Off
“StartV:2hr”
Off, 4.0V–60.0V
Off
“StartV:24hr”
Off, 4.0V–60.0V
Off
“StopBattV”
Off, 4.0V–60.0V
Off
“Enable Temp1”
On, Off
Off
“Enable Temp2”
On, Off
Off
“Enable Load”
On, Off
Off
“Start Load”
10.0A–33.0A
10.0A
“Stop Load”
7.0A–28.0A
7.0A
“Stop Absorb”
On, Off
On
“Stop Float”
On, Off
Off
“Max Run Time” 2hours–8hours
3hours
“Exercise Per”
0days (Off)–250days
21days
“Exercise Dur”
1min–250min
30min
“Exercise Time”
12:00AM–11:59PM (12-hour clock)
00:00–23:59 (24-hour clock)
9:00AM (12-hour clock)
9:00 (24-hour clock)
Summary of Contents for Automatic Generator