MomentaryRun Mode
975-0082-01-01
C–3
MomentaryRun Mode
For generators with MomentaryRun mode starting types (Type 11):
•
Relay 1 (Run/Stop relay) can be used for two-wire configured
generators.
•
Relay 2 has no unique function in this configuration, but it is easiest
to leave it doing the cranking so that another configuration is not
required for it.
•
Preheat will generally not be used in this configuration.
•
The Preheat will never overlap the Crank Time.
•
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
•
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
Figure C-2
MomentaryRun mode timing diagram
Stop
Run
Time
Relay1: Momentary Run
Relay2: Start (Cranking)
Relay3: Preheat (Glow)
Crank
Start
Preheat