PulseStop Mode
975-0082-01-01
C–5
•
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
•
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
•
To get the ShutDown Bypass on Relay 3 with no preheat, Relay 3
must be configured for Preheat with ShutDown Bypass and have the
Preheat time set to zero.
•
StartStop mode is essentially the same as GlowStop mode with no
preheat on Relay 1.
PulseStop Mode
For generators with PulseStop mode starting types (Type 13):
•
Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground
for three-wire configured generators.
•
If Relay 3 is configured for Preheat, the signal only shows up on
Relay 3.
•
The Preheat on Relay 3 will not overlap the Crank Time if ShutDown
Bypass is not enabled.
•
If the ShutDown Bypass is enabled, the Preheat on Relay 3 will
remain high for the Crank Time and for the ShutDown Bypass period
after cranking.
•
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
•
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
•
To get the ShutDown Bypass on Relay 3 with no preheat, Relay 3
must be configured for Preheat with ShutDown Bypass and have the
Preheat time set to zero.
Figure C-4
StartStop mode timing diagram
Stop
Start
Time
Preheat
Relay1: Stop
Relay2: Start (Cranking)
Relay3: Preheat (Glow)
& Shutdown Bypass
Crank
Shutdown
Bypass
Summary of Contents for Automatic Generator
Page 1: ...Automatic Generator Start Owner s Guide...
Page 2: ......
Page 3: ...Automatic Generator Start Owner s Guide...
Page 8: ...vi...
Page 22: ...1 8...
Page 54: ...Configuration 3 6 975 0082 01 01 Figure 3 5 Auto Gen Start menu contents...
Page 102: ...A 4...
Page 118: ...WA 6...
Page 122: ...IX 4...
Page 123: ......