![background image](http://html1.mh-extra.com/html/xantrex/automatic-generator/automatic-generator_owners-manual_3170888039.webp)
Installing the Auto Gen Start
975-0082-01-01
2–17
Type 8
Type 8 will work with both two-wire and three-wire run mode
configurations and is intended for Northern Lights and Fisher Panda
generators. Type 8 is identical to Type 7 except that it provides no preheat
signal before cranking. See Figure 2-8 and Figure 2-9 for wiring
diagrams.
Table 2-9
Type 8 relay and timing preset configurations
Relay 1 mode
Run
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Shutdown bypass time
0 s
Start tries
3