System 182
Relay outputs
6 - 5
ba75503e07
04/2012
6.3
Basic information on relay functions
In this chapter, you will find general basic information concerning the
following relay functions:
Event monitoring (see section 6.3.1)
Limit indicator (see section 6.3.2)
Proportional output (see section 6.3.3)
6.3.1
Event monitoring
When using a relay for event monitoring, a relay action (
Open
,
Close
)
occurs when the monitored event takes place.
This function is suitable, e.g. for the monitoring of errors in the system.
If an event takes place, the relay works as an alarm contact.
Note
For monitoring functions, use the relay preferably as an opener. In the
case of an error, the relay opens. As a result, the monitoring function
operates even if, e.g. the supply voltage fails.
6.3.2
Limit indicator
With a limit indicator, a relay switches when a specified limiting value is
exceeded or undercut.
Limit indicators can be used in the following way:
Monitoring a limiting value using a relay:
when a limiting value (upper or lower limiting value) is exceeded or
undercut, a relay switches. The
Open
or
Close
relay actions are
possible in each case (see page 6-6).
Monitoring two limiting values using two relays:
If the upper limiting value is exceeded or undercut, a relay switches,
and if the lower limiting value is exceeded or undercut, another relay
switches. The
Open
or
Close
relay actions are possible in each case
Note
If the simple monitoring function (
Open
,
Close
) with one or two relays
is not sufficient, use proportional output (see section 6.3.3).
Summary of Contents for DIQ/S 182-PR
Page 6: ...Contents System 182 0 4 ba75503e07 04 2012 ...
Page 10: ...Overview System 182 1 4 ba75503e07 04 2012 ...
Page 14: ...Safety instructions System 182 2 4 ba75503e07 04 2012 ...
Page 78: ...Operation System 182 4 18 ba75503e07 04 2012 ...
Page 84: ...The SETTINGS menu System 182 5 6 ba75503e07 04 2012 ...
Page 110: ...Relay outputs System 182 6 26 ba75503e07 04 2012 ...
Page 122: ...PROFIBUS connection System 182 7 12 ba75503e07 04 2012 ...
Page 124: ...Maintenance and cleaning System 182 8 2 ba75503e07 04 2012 ...
Page 130: ...What to do if System 182 9 6 ba75503e07 04 2012 ...
Page 142: ...Accessories and options System 182 11 2 ba75503e07 04 2012 ...
Page 146: ...Appendix store separately if required System 182 13 2 ba75503e07 04 2012 ...