Relay outputs
System 182
6 - 24
ba75503e07
04/2012
Canceling the cleaning
A running cleaning cycle is canceled:
Automatically
– If the sensor switches to the inactive condition during the cleaning
cycle
Manually
– By pressing
c
– By switching on the maintenance condition
Each time the cleaning cycle is canceled, the relay opens immediately.
If the cleaning cycle is canceled automatically, the outputs linked to the
sensor are released immediately.
If the cleaning cycle is canceled manually, the sensor is in the
maintenance condition. The linked outputs are only released after the
maintenance condition was terminated manually.
The next cleaning cycle will be performed at the time set up.
Note
In case of a power failure, all relays open. The cleaning cycle is
canceled. The outputs linked with the sensor change to the non-active
condition (see section 6.5.2). As soon as the power is available, the
outputs are released again. The next cleaning cycle will be performed
at the time set up.
6.4.9
Manual control
Function
With the
Manual control
function, you can test the operativeness of an
instrument that is connected to the relay. To do so, close or open the
relay manually and, while doing so, check the behavior of the
connected instrument.
Note
The settings for other functions in the
Relay function
menu, as for
example
Frequency output
and
Pulse-width output
, are retained while
the
Manual control
is carried out.
Setting
Selection/Values
Explanation
Relay function
Manual control
The selected relay action
is carried out with
Speichern u. Beenden
.
Action
Open
Close
Relay action
Summary of Contents for DIQ/S 182-PR
Page 6: ...Contents System 182 0 4 ba75503e07 04 2012 ...
Page 10: ...Overview System 182 1 4 ba75503e07 04 2012 ...
Page 14: ...Safety instructions System 182 2 4 ba75503e07 04 2012 ...
Page 78: ...Operation System 182 4 18 ba75503e07 04 2012 ...
Page 84: ...The SETTINGS menu System 182 5 6 ba75503e07 04 2012 ...
Page 110: ...Relay outputs System 182 6 26 ba75503e07 04 2012 ...
Page 122: ...PROFIBUS connection System 182 7 12 ba75503e07 04 2012 ...
Page 124: ...Maintenance and cleaning System 182 8 2 ba75503e07 04 2012 ...
Page 130: ...What to do if System 182 9 6 ba75503e07 04 2012 ...
Page 142: ...Accessories and options System 182 11 2 ba75503e07 04 2012 ...
Page 146: ...Appendix store separately if required System 182 13 2 ba75503e07 04 2012 ...