13-2
Operation via SNMP
13.3. Configuration via SNMP
VMR/NPS User accounts can be viewed, created, modified, and deleted via SNMP.
User accounts are arranged in a table of 128 rows, and indexed 1-128. User account
parameters, as seen through the SNMP, are summarized below.
Note:
Current and Power Monitoring features are not available on NPS units.
•
userTable::userName
– 32 character username
•
userTable::userPasswd
– 16 character password
•
userTable::userAccessLevel
– Account access level.
0
– View Access
1
– User Access
2
– Superuser Access
3
– Administrator Access
•
userTable::userLocalAccess
– A string of 16 characters, with one character
for each of the 16 possible plugs on the VMR/NPS unit. A ‘
0
’ indicates that the
account
does
not
have access to the plug, and a ‘
1
’ indicates that the user
does
have access to the plug.
•
userTable::userGroupAccess
– A string of 54 characters, with one character
for each of the 54 possible plug groups in the system. ‘
0
’ indicates that the account
cannot
access the group, and ‘
1
’ indicates that the user
can
access the group.
•
userTable::userSerialAccess
– Access to the serial interface
0
– No access
1
– Access
•
userTable::userTelnetSshAccess
– Access to the Telnet/SSH interface.
0
– No access
1
- Access
•
userTable::userOutboundTelSshAccess
– Access to Outbound Telnet/SSH
0
– No access
1
- Access
•
userTable::userWebAccess
– Access to the Web interface.
0
– No access
1
- Access
•
userTable::userCurrentPowerMetering
– (VMR Only) Access to the systems
current/power metering.
0
– No access
1
– Access
•
userTable::userCallbackNum
– 32 character callback number for account.
•
userTable::userSubmit
– Set to
1
to submit changes.