Connecting the immersion heater (Heaters conform to 
EN60335.2.73)

It is essential that the water level within the tank or cylinder is such that 
water fully covers the heating elements to a depth of at least 100 mm. 
Under no circumstances must the heater be permitted to run dry - 
serious damage may result to the heater in addition to danger of 
personal injury & damage to property.

Check the heater for possible leakage before wiring. See below for 
schematic wiring diagram.

Wire the heater through a double-pole fused spur, having contact 
separation of at least 3 mm, with a minimum breaking capacity of 
13 Amps. 

Use a rigid cable, 2 m long max, with 1.5 mm

2

 cross-section and a 

temperature resistance of at least 85°C. Rubber Insulated HOFR 
Sheathed, complying with BS6141 Table 8. It must be fully earthed. 
Ensure all terminal connections are securely made. Do not however use 
excessive force when tightening the terminal screws.

NEMKO Approval will only apply to this heater if the Thermowatt RTS 
plus thermostat is used.

Immersion heater conforms with EEC Directive 76/889 for Radio 
Interference and comply with BS800: 1977.

WIRING THE IMMERSION HEATER:

▶ Remove the terminal cover from the immersion heater. Use the 

accessories supplied in the plastic bag located under the cover of the 
immersion heater to complete the wiring.

Fig. 16   Wiring diagram

E

Earth (Green/Yellow)

N

Neutral (Blue)

L

Live (Brown)

Fig. 17   Rigid cable end preparation

E

Earth (Green/Yellow)

N

Neutral (Blue)

L

Live (Brown)

▶ Provide 90 mm length for the Live (L) and Neutral (N) cables and 

bare the end of each cable 8 mm minimum.

▶ Provide 105 mm length for the Earth cable (E) and bare the end of 

the cable 20 mm minimum. Make a circle with the end of the Earth 
cable (E) to turn around the earth stud (1) to ensure a full contact 
between the cup washer (6) and the plain washer (4) (refer to the 
fitment of earth cable to stud).

▶ Fit the Live and Neutral cables on the thermostat.

Fig. 18   Fitment of earth cable to stud

[1]

Earth stud

[2]

Nuts (x2) *

[3]

Shake-proof washer *

[4]

Plain washer *

[5]

Earth cable

[6]

Cup washer *

[*]

supplied in the plastic bag

▶ Ensure the mains voltage corresponds to the voltage 

rating of the heater as shown on the rating label on 
the terminal cover.

▶ Only use rigid wires 1.5 mm

2

 for main supply. 

Flexible wire may cause poor electrical connection to 
the heater, resulting in overheat.

▶ When connecting the thermostat please ensure the 

male pins are securely located within the female 
sockets.

▶ Accessories (washers, cable grip, screws…) 

delivered in the plastic bag under the terminal cover 
of the heater have to be used to complete the 
connection to the earth and to fix the rigid cable.

DANGER: 

Risk of electric shock!

▶ Isolate from mains supply.

▶ This heater must be earthed.

E

N

L

AQU-32-3W

L

N

E

E

AQU-33-3W

105

90

20

8

L = 2 m max

(3x1.5 mm² - 85 °C)

Summary of Contents for Greenstore TC Cylinder 150 litre

Page 1: ...Installation and maintenance instructions Twin Coil Indirect Unvented Hot Water Cylinder Greenstore TC Cylinder Series 6 720 645 525 00 1O 150 180 210 250 300 litre 6 720 805 339 2014 09 UK...

Page 2: ...appliance 13 3 7 2 Connection of the primary appliance or solar system 13 3 7 3 Connection on the water side 13 3 7 4 DHW secondary circulation 13 3 7 5 DHW expansion vessel 14 3 7 6 Installing the d...

Page 3: ...st install commission and maintain this equipment Only use the cylinder for heating domestic hot water Function Observe these installation and maintenance instructions to ensure correct operation Neve...

Page 4: ...nput reduces the cycling of the heating appliance and reduces the cylinder heat up time 2 2 Intended use Only use the cylinder for heating domestic hot water Any other application will be considered i...

Page 5: ...ling Incaseswherethewaterhardnessisveryhigh over450 ppm a water softener must be used to protect the cylinder against rapid development of scale Corrosion protection Any water softener shall be instal...

Page 6: ...10 Cylinder flow return primary appliance solar 22 mm Fig 3 Physical and connection dimensions AQU 24 3W 6 1 2 2 3 4 5 7 7 8 9 10 10 J 45 35 25 45 AQU 25 3W I B F G H E C D A 15 Cylinder Part number...

Page 7: ...Product details 6 720 805 339 2014 09 7 clearance dimensions Fig 4 Recommended minimum wall clearances all dimensions in mm 80 6 720 645 525 06 1O 50 50 50 180...

Page 8: ...9 3 9 Heat exchanger surface m2 0 657 0 657 0 845 0 845 0 845 Maximum heating water temperature C 120 120 120 120 120 Maximum operating pressure inside the upper indirect coil bar 6 6 6 6 6 Heat exch...

Page 9: ...re of 55 45 frost protection down toapproximately 30 C thepressuredropisapproximately1 3times the value for tap water Fig 5 TC 150 and TC 180 p Pressure drop V Heating water volume Fig 6 TC 210 TC 250...

Page 10: ...or human consumption Installation BS EN 806 5 2012 Specifications for installations inside buildings conveying water for human consumption Operation and maintenance BS 8558 2011 Guide to the design in...

Page 11: ...ary heat source SP Solar circuit pump optional accessory SV1 Temperature and Pressure relief valve SV2 Expansion relief anti vac valve G3 kit supplied SWC Terminal box S solar Twin coil cylinder TB So...

Page 12: ...in the lower section of the cylinder 6 720 645 525 05 1O 2 1 3 Solar thermal system yes yes no no System type S plan or Y plan with internal three way valve S plan or Y plan with internal three way v...

Page 13: ...ockattimeofcommissioning the unit an air vent may be required The coil must be able to be drained via a suitable valve 3 7 3 Connection on the water side Install the cold water inlet control group as...

Page 14: ...etydeviceunlessitstotalequivalenthydraulicresistanceexceeds that of a straight pipe 9 m long i e discharge pipes between 9 m and 18 m equivalent resistance length should be at least two sizes larger t...

Page 15: ...herefore calculate the next largest size Maximum resistance allowed for a straight length of 28 mm copper discharge pipe D2 from a G1 2 temperature relief valve is 18 m Subtract the resistance for 4 N...

Page 16: ...diagrams reference must be made to the appropriate manufacturers installation instructions for the products installed along side this unit Products must be wired to meet all current regulations with...

Page 17: ...MUST incorporate a gravity break check valve G3 protection from excessive solar input Additional wiring for solar pump stations without a gravity break check valve A solar high limit thermostat will i...

Page 18: ...g 15 Greenstar i System Compact wiring example ST10 DIVERTER VALVE MOTOR PLUG CYLINDER TEMPERATURE SENSOR SUPPLIED IN DIVERTER KIT F1 F3 F2 ST10 ST6 LEAVE LINK Greenstar CDi Classic System boiler ONLY...

Page 19: ...ofthe immersion heater to complete the wiring Fig 16 Wiring diagram E Earth Green Yellow N Neutral Blue L Live Brown Fig 17 Rigid cable end preparation E Earth Green Yellow N Neutral Blue L Live Brown...

Page 20: ...solar controller Whenthereisariskoffrostandthecylinderistakenoutofuse drain the cylinder completely including its lower section 5 2 Draining the cylinder To drain either the domestic water system or t...

Page 21: ...ng or repair Vent the heating solar and DHW sides 8 Spare parts list 9 The Guarantee The Greenstore stainless steel cylinder carries a fully transferable 25 year guarantee against faulty material or m...

Page 22: ...pressure relief valve and expansion valve been tted and discharge tested Yes No The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes Are all...

Page 23: ...er Name Company Name Telephone No Gas Safe Register No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments Signature Date Engineer Name Company Name Telephone...

Page 24: ...59 Worcester Bosch Group is a brand name of Bosch Thermotechnology Ltd worcester bosch co uk 6 720 805 339 WORCESTER BOSCH GROUP TECHNICAL SUPPORT 0330 123 3366 APPOINTMENTS 0330 123 9339 SPARES 0330...

Reviews: