Settings in the service menu
Greenstar 8000 Style – 6720883864 (2019/02)
52
Pump overrun
• 1...
2
...60 minutes
• 24 h: 24 hours
Run-on time of the heating pump: pump run-on time
begins at the end of the heat requirement.
Min.syst.pressure
• 1...
2
...3 bar
Target pressure
• 0.8...
1.3
...1.8 bar
Special function
Ventilation func.
•
Off
• Auto
• On
The ventilation function can be activated after
maintenance.
During ventilation, the following appears in the info area
of the standard display Ventilation func.
Siphon fill. prog.
• Off (only permissible during maintenance)
•
On, boiler min.
• On, heating min.
The siphon filling program is activated in the following
cases:
• On, boiler min.: the appliance is switched on using the
On/Off switch.
• On, heating min.: The burner was not in use for at least
28 days.
• The operating mode is switched from summer to
winter mode.
The next time there is a heat requirement for heating, the
appliance is held at low output for 15 minutes. The siphon
filling program remains active until the appliance has
completed 15 minutes of operation at low output.
During the siphon filling program the following appears in
the info area of the standard display Siphon fill. prog.
3-WV mid. pos.
•
No
• Yes
The function ensures that the system is fully drained and
that the motor can be easily removed. The 3-way valve
remains at the centre position for approx. 15 minutes.
Autom. filling
• Autom. filling:
No
| Yes
• Min. Sys. Pres.
• Target Sys. Pres.: 1.0…
1.5
…2.5 bar
• Max. refill time: 5...
30
...240 seconds
• Blocking time: 1...
12
...52 weeks
• Max. refills: 1...
5
...20
• Reset refilling
The automatic filling function ensures that the operating
pressure is maintained. If the operating pressure drops
below the set value, the filling valve opens until the set set
pressure is reached.
To protect against e.g. leakage, the filling valve closes in
the following cases:
• No pressure increase can be measured
• The set filling time is exceeded
The filling valve does not open within the set blocking
time or when the maximum number of fillings is reached.
Maintenance
Maintenance type
• Without
• Burner run time
• Boiler run time
• Service date
• Landlord
Landlord
:
This menu item allows a date to be set for annual service/
maintenance (End date). The service display appears as a
reminder 30 days before the scheduled date. A contact
telephone number (Installer tel. no.) is shown together
with service display. The tenant should call this number to
arrange a suitable maintenance date. A second reminder
appears at the scheduled date. If the service display is not
reset by the service engineer, the control unit limits the
functions 14 days after the scheduled date.
Reduced functions are set at Maint. reminder:
• DHW reduced: reduced comfort (max. 35 °C flow
temperature)
• Boiler off: central heating and hot water functions are
set off.
Limit values
Max. flow temp.
• 30...
88 °C
Limits the adjustment range for the flow temperature.
Max. DHW temp.
• 30...
60 °C
Limits the adjustment range for the hot water
temperature.
Min. boiler outp.
•
"Minimum rated output"
…"maximum rated
output"
Minimum heat output
Menu item
Settings/adjustment range
Comment/restriction