Settings in the service menu
51
Greenstar 8000 Style – 6720883864 (2019/02)
7.2.3
Settings menu
The menu is adapted to your system automatically. Some menu items are
only available if the system has been set up accordingly. The menu items
are only displayed in systems in which the corresponding system
components are installed, e.g. automatic filling facility or Key Timer.
The factory settings are
highlighted
in the following table.
Menu item
Settings/adjustment range
Comment/restriction
Heating
Max. heat output
Maximum released heating output [%].
On natural gas appliances:
▶ Measure the gas rate.
▶ Compare the measurement with the setting tables (
▶ Correct deviations.
Standby time
• 3…
10
…60 minutes
The time interval determines the minimum delay between
starting and restarting the burner.
Clock inh. T. off
Clock inh. T. on
• 2 …
6
… 15 Kelvin
• -15...
-6
...-2 Kelvin
Temperature standby period.
The difference between the current flow temperature and
the set flow temperature until the burner is switched on or
off.
Hot water
Turbine signal del.
•
0.50
...4.00 seconds
The delay prevents sudden changes in the water supply
pressure from causing the burner to briefly operate
although no water is drawn off.
DHW start del.
•
0
…50 seconds
The delay concerns heating operation in systems in which
the DHW outlet of the solar-heated DHW cylinder is
connected to the cold water inlet of a combi boiler. DHW
heating by the combi boiler will be suppressed expecting
that solar thermal DHW will reach the hot water
temperature sensor prior eliminating the need to run the
boiler. This avoids unnecessary operation of the combi
boiler. Set the heating delay in accordance with system
conditions.
Preheat
• 0…
1
…30 minutes
The heating mode is disabled for this period of time
following DHW heating.
Pump
Pump range map
• Output dependent0: pump rate proportional
to thermal output
• Delta-P dependent 1: constant pressure
150 mbar
• Delta-P dependent 2: constant pressure
200 mbar
•
Delta-P dependent 3: constant pressure
250 mbar
• Delta-P dependent 4: constant pressure
300 mbar
• Delta-P dependent 5: constant pressure
350 mbar
• Delta-P dependent 6: constant pressure
400 mbar
▶ Set low pump curve to save energy and avoid possible
flow noise (
Pump ctr. mode
• Energy saving
•
Heat demand
• Saving energy: intelligent heating pump stop in
heating systems with weather-compensated
controller. The heating pump is only switched on
when needed.
• In case of a heat requirement: the flow temperature
controller switches the heating pump. When there is a
heat energy demand, the heating pump starts up with
the burner.
Min. output
•
10
...100 %
Pump rate at minimum thermal output. Only available
with pump characteristic map 0.
Max. output
• 10...
100
%
Pump rate at maximum thermal output. Only available
with pump characteristic map 0.