LEMCOM EtherNet/IP™ - User manual
EtherNet/IP™
COVAL - LMEIP-UK-D-1155UM0067
33/42
8.9.8
Input instance 141
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
↓ HEARTBEAT ↓
Byte 0
-
-
-
-
-
-
-
Heartbeat
↓ SELECTED MODULE IN INSTANCE 111 (DIAGNOSTIC REQUEST ACKNOWLEDGEMENT) ↓
Byte 1
Diagnostic data given in bytes 34 to 77 are related to module number given here
Byte 2
To
Byte 33
Refer to bytes 2 to 33 described for Instance 140
↓ DIAGNOSTIC DATA OF THE SELECTED MODULE IN INSTANCE 111 ↓
Bytes 34-37
External vacuum counter
: Number of external activation of the vacuum valve (customer controls only / sent by
PLC, LEMCOM MANAGER, Web server)
Most significant byte on byte 37.
Bytes 38-41
Internal vacuum counter
: Total number of activation of the vacuum valve (external/customer co automatic
controls due to ASC).
Most significant byte on byte 41.
Bytes 42-45
Blow-off counter
: Number of activation of the blow-off valve (external/customer co automatic blow-off).
Most significant byte on byte 45.
Bytes 46-49
Gripping counter
: Number of parts handled by the vacuum pump.
Most significant byte on byte 49.
Bytes 50-53
Lost parts counter
: Number of lost parts during handling.
Most significant byte on byte 53.
Bytes 54-57
ASC counter
: Number of activation of the Air Saving Control (ASC) system.
Most significant byte on byte 57.
Bytes 58-61
ASC errors counter
: Number of interruption of the regulation system due to vacuum leakage (switch to permanent
suction).
Most significant byte on byte 61.
Bytes 62-65
Com. errors (local)
: Number of communication errors detected on the CAN local bus.
Most significant byte on byte 65.
Bytes 66-69
Com. errors (bus)
: Number of communication errors detected on the customer fieldbus (Master module only).
Most significant byte on byte 69.
Bytes 70-73
Power supply errors
: Power supply monitoring and warning when voltage is below the Power supply threshold
(21,6V by default).
Most significant byte on byte 73.
Bytes 74-75
Power supply measurement
: given in tenth of volts
Most significant byte on byte 75.
Bytes 76-77
Internal temperature measurement
Most significant byte on byte 77.
Table 20 - Data mapping - Input instance 141