Table 32 Modulating speed characteristics
The head (pressure) is reduced at falling heat demand and increased at
rising heat demand.
13.2
Tech data
Table 33 Heat interface unit specifications
Table 34 Measured temperatures and volumetric flow rates
Table 35 Heat meter integrator technical data
Temperature Sensor
Table 36 Primary circuit NTC central heating flow and return
temperature sensor
Setting
Maximum head (nominal)
Maximum P1 (nominal)
Curve 1
4 m
25 W
Curve 2
5 m
33 W
Curve 3
6 m
39 W
HIU (...) HIU K (...)
Weight excluding packaging
kg
31
33
Weight including packaging
kg
34
36
Minimum inlet pressure to achieve
nominal DHW flow rate
bar
1.5
2.0
DHW output (50°C @ 40 K rise)
kW
41.8
58.6
DHW output (90°C primary, 60°C DHW)
kW
52,3
73,3
Heating output
kW
1 - 15
Maximum flow temperature of primary
circuit
°C
70
Maximum flow temperature of heating
circuit
°C
70
Maximum DHW temperature
°C
60
Maximum operating pressure
bar
10
pH value range, approx. (heating)
6 – 9.5
Maximum primary differential pressure
(with internal DPCV)
bar
4 (without internal
DPCV: 0,8)
Maximum DHW volumetric flow rate
L/min
15
21
Maximum volumetric flow rate of primary
circuit
l/s
0.35
0.38
Max. ambient temperature
°C
35
Expansion vessel
l
5
Expansion vessel charge
bar
0.75
electric
Electrical power supply voltage
AC V
230
Frequency
Hz
50
Maximum power consumption
W
41.3
Standby power consumption
W
3.1
Appliance protection rating
IP
X4D
Primary circuit
65 °C
1)
1) DHW temperature 40°C with 30 K increase
70 °C
2)
2) DHW temperature 45°C with 35 K increase
80 °C
3)
3) DHW temperature 50°C with 40 K increase
HIU (...)
Potable Hot Water output
kW
31.3
36.6
41.8
Volumetric flow rate of primary
circuit
l/s
0.17
0.18
0.17
Primary circuit return temperature
°C
19.3
21.9
22.3
Primary circuit pressure loss
without heat meter
kPa
14
16
15
Primary circuit pressure loss with
heat meter
kPa
20.5
24
21
HIU E (...)
Potable Hot Water output
kW
31.3
36.6
41.8
Volumetric flow rate of primary
circuit
l/s
0.17
0.18
0.17
Primary circuit return temperature
°C
19.3
21.9
22.3
Primary circuit pressure loss
without heat meter
kPa
22
26
22
Primary circuit pressure loss with
heat meter
kPa
28
33
30,5
HIU KE (...)
Potable Hot Water output
kW
44.0
51.3
58.6
Volumetric flow rate of primary
circuit
l/s
0.23
0.25
0.24
Primary circuit return temperature
°C
18.6
20.8
21.1
Primary circuit pressure loss
without heat meter
kPa
37.4
45.1
41.3
Primary circuit pressure loss with
heat meter
kPa
51
61.5
56.4
Integrator
Temperature Sensor
Temperature sensors
PT500
Diameter
Ø 5.2 mm
Cable length
1.5 m
Temperature range
5...130 °C
Starting temperature differential
0.125 K
Flow measurement cycle with mains supply
1/8 s; with D-cell
battery: 1 s
Permissible temperature
Operation (<35 °C has a positive effect on lifetime)
5...55 °C
Storage (>35 °C max. 4 weeks)
-25...60 °C
Min. temperature difference
min
3 K
Max. temperature difference
max
177K
Resistance
Temperature
°C
Resistance
Temperature
°C
29529
0
8186
30
18787
10
5586
40
12257
20
3889
50