Vertex-Pro Motor-Driven Compressor Control
Manual 26489V1
22
Woodward
5.1.2—Module Configuration
Hardware Configuration.
The Module Configuration Switch (S2) must be
configured properly for CPU mode (main rack, address 0x000) operation. This
module will be factory configured appropriately.
Network Type
Switch Function
OFF RTN Network 172.20.x.x
ON RTN Network 10.250.x.x
Module Config
Addr Switch Function
0 000 CPU, MAIN CHASSIS
1 001 RTN, CHASSIS-X1
2 010 RTN, CHASSIS-X2
3 011 RTN, CHASSIS-X3
4 100 RTN, CHASSIS-X4
5 101 RTN, CHASSIS-X5
6 110 RTN, CHASSIS-X6
7 111 RTN, CHASSIS-X7
*SWITCH POSITIONS SHOWN AT CPU DEFAULTS
Module Config
Switches
NETW
O
R
K
TYPE
S2
1
2
3
4
LSB
ON
(o
pen)
OFF
It is recommended to verify proper switch settings before installing
the module in the system and when troubleshooting CPU-related
issues.
If the CPU module is incorrectly configured for RTN mode, Ethernet
ports #1 and #2 are NOT active and AppManager will not be available.
Network Type.
The Network Type setting is factory set OFF to
automatically configure the RTN communication port IP addresses to the
172.20.x.x series.
It is recommended to verify proper switch settings before installing
the module in the system and when troubleshooting CPU or RTN
related issues.
The Network Type setting on all CPU and Remote RTN modules in
the system must match for proper system operation.
The customer network attached to Ethernet #1 or #2 may already use
the RTN port addresses of 172.20.x.x. In this case, the Network Type
switch should be configured ON to use the 10.250.x.x RTN port
addresses.
Network Configuration.
Ethernet ports (ENET1, ENET2) can be configured for
the customer network as desired. The RTN ports (RTN1, RTN2) are reserved for
communicating with Woodward Real Time Network devices such as expansion
racks. See the on-site Network Administrator to define an appropriate I/P address
configuration for ENET1 and ENET2.
This module has been factory configured with fixed Ethernet IP
addresses of
Ethernet #1 (ENET1) =
172.16.100.1
, Subnet Mask =
255.255.0.0
Ethernet #2 (ENET2) = 192.168.128.20, Subnet Mask =
255.255.255.0
Summary of Contents for Vertex-Pro
Page 10: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 viii Woodward ...
Page 103: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 93 Appendix C Declarations ...
Page 104: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 94 Woodward ...
Page 105: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 95 ...
Page 106: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 96 Woodward ...
Page 107: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 97 ...
Page 111: ......