Manual 26489V1
Vertex-Pro Motor-Driven Compressor Control
Woodward
77
9.2.9—Connection of Cabinet to Installation Ground
Ensure the cabinet enclosure is electrically grounded to the plant ground
system. Use as large a conductor as is possible. Use plant guidelines.
9.2.10—DIN Rail Grounding
Provide Chassis ground to FTMs using a DIN rail ground clip.
Install one each of these clips at the FTM end closest to the Earth ground
connection point.
Use largest gauge wire allowed by Clip and FTM.
Maximum length of ground wire shall not exceed 5 cm/2”
9.2.11—Equipment Bonding
DIN rail shall be electrically connected to structural frame (<2.5 m
Ω
) once
every 30 cm/12”.
Use a minimum of 2 screws to bond a DIN rail to cabinet frame.
Equipment chassis shall be electrically connected to structural frame (<2.5
m
Ω
).
9.2.12—Safety Ground Wire Installation
Safety wires shall be routed against the grounded cabinet structure. Locate
safety ground wire 6” from unshielded cabling, 3” from internal shielded
cabling, and 15 cm/6” from any I/O cabling exiting the cabinet.
9.2.13—Installation of Other Equipment, Fans, Meters, etc.
Shield Termination Schemes
See Application Note B51204 for this information.
Summary of Contents for Vertex-Pro
Page 10: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 viii Woodward ...
Page 103: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 93 Appendix C Declarations ...
Page 104: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 94 Woodward ...
Page 105: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 95 ...
Page 106: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 96 Woodward ...
Page 107: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 97 ...
Page 111: ......