Module: IEC60870-5-103
Global Protection Parameters of the IEC60870-5-103
Parameter
Description
Setting range
Default
Menu path
Slave ID
Device address (Slave
ID) within the bus
system. Each device
address has to be unique
within a bus system.
1 - 247
1
[Device Para
/IEC 103]
t-call
If there is no request
telegram sent from
Scada to the device after
expiry of this time - the
device concludes a
communication failure
within the Scada system.
1 - 3600s
60s
[Device Para
/IEC 103]
Transm priv meas val
Transmit additional
(private) measuring
values
inactive,
active
inactive
[Device Para
/IEC 103]
Baud rate
Baud rate
1200,
2400,
4800,
9600,
19200,
38400,
57600
19200
[Device Para
/IEC 103]
EN MRU4 10/09
Page 189