Field Parameters
Field Parameters
Field Para
Within the field parameters you can set all parameters, that are relevant for the primary side and the mains
operational method like frequency, primary and secondary values and the star point treatment.
Parameter
Description
Setting range
Default
Menu path
Phase Sequence
Phase Sequence
direction
ABC,
ACB
ABC
[Field Para]
f
Nominal frequency
50Hz,
60Hz
50Hz
[Field Para]
VT pri
Nominal voltage of the
Voltage Transformers at
the primary side
60 - 500000V
10000V
[Field Para]
VT sec
Nominal voltage of the
Voltage Transformers at
the secondary side.
60.00 - 400.00V
100V
[Field Para]
VT con
This parameter has to be
set in order to ensure the
correct assignment of the
voltage measurement
channels in the device.
Phase to Earth,
Phase to Phase
Phase to Earth
[Field Para]
EVT pri
Primary nominal voltage
of the e-n winding of the
voltage transformers,
which is only taken into
account in the direct
measurement of the
residual voltage (GVT
con=measured/broken
delta).
60 - 500000V
10000V
[Field Para]
EN MRU4 10/09
Page 209