Displaying / modifying control parameters
with Wolf control accessories
The higher burner output in DHW mode can be adjusted within the modulation
range. The setting relates to the maximum heating output in kW (see table
"Limiting maximum heating output").
Upper burner output DHW
Parameter HG03
HG03
100
Factory setting: 100
Setting range: 1 to 100
The higher burner output in heating mode can be adjusted within the modulation
range. The setting relates to the maximum heating output in kW (see table
"Limiting maximum heating output").
Upper burner output Hz
Parameter HG04
HG04
100
Factory setting: 100
Setting range: 1 to 100
Pump operating mode 0:
Heating circuit pump for heating systems without cascade control and
without low loss header
The boiler pump runs constantly when there is a heat demand. When the heat
has been switched off via the room thermostat or remote control, the boiler
pump runs for the set time (pump run-on Hz, parameter HG07).
Pump operating mode
Parameter HG06
HG06
0
Factory setting: 0
Setting range: 0 / 1 / 2
Pump operating mode 1:
Feed pump for heating systems with cascade control and/or low loss
header/buffer (manifold sensor essential)
Boiler pump becomes the feed pump.
The manifold sensor affects the heating operation as well as the cylinder heating
(please note: only cylinder mode possible). The boiler pump will not run for a
general heat demand, but rather only when there is a burner demand in the
heating operation, with pump run-on according to parameter HG07.
VL Sensor 1
Three-way valve
Header
Manifold sensor E1
VL Sensor 2
A1 as heating
circuit pump
A1 as primary
cylinder pump
DHW cylinder
Hydraulic scheme:
Gas fi red boiler
Boiler
pump
or