22
3062347_0309
Parameter overview / setting report
Column 1 settings apply to control accessories ART, AWT
Column 2 settings apply to Wolf control system with BM programming module
(Setting and function of the most important functions on the following pages, further description,
see BM installation instructions.)
Parameters
Setting range
Factory setting Individual settings
Column 1
Column 2
HG00
Adjusting flue lengths
1 to 5
4
GB05
A09
Frost protection limit
-20 to +10 °C
+2 °C
GB01
HG01
Burner switching differential
5 to 25 K
8 K
HG02
Lower burner output heating
1 to 100%
1%
HG03
Upper burner output DHW
1 to 100%
100%
GB04
HG04
Upper burner output heating
1 to 100%
100%
GB06
HG06
Pump operating mode
0 to 2
0
GB07
HG07
Boiler circuit pump run-on time
0 to 30 min
1 min
GB08
HG08
Maximum boiler temperature, heating
40 to 90 °C
80 °C
GB09
HG09
Burner cycle block
1 to 30 min
7 min
HG10
eBUS address (display only)
1 to 4
1
HG11
DHW quick start temperature
10 to 60 °C
10 °C
HG12
Gas type, 1=natural gas 0=LPG
0 to 1
1
HG13
Programmable input E1
1 to 11
1
HG14
Programmable output A1
0 to 15
6
HG15
Cylinder hysteresis
1 to 30 K
5 K
HG20
Max. cylinder heating time
0 to 5 h
2 h
HG21
Minimum boiler water temperature TK-min >40 °C*
20 to 60 °C
40 °C
HG23
Maximum DHW temperature
60 to 80 °C
65 °C
HG25
Boiler overtemperature during DHW cylinder heating
0 to 40 K
20 K
HG70
Manifold sensor (display only)
HG80-89 Fault history
The control parameters can only be modified or displayed via Wolf control accessories with eBUS
capability. For installation and procedures, check the operating instructions of the relevant accessories.
To prevent damage to the heating
system, cancel night setback when
outside temperatures fall below -12 °C. If
this rule is not observed, ice may form on
the flue outlet which may cause injury to
individuals or material losses.
Modifications must only be carried out by
a recognised heating contractor or by the
Wolf customer service
.
L.h. rotary selector
Program selection
Display
R.h. rotary selector
Temperature selection
Info key
Single cylinder
heating key
Setback key
Heating key
Note
BM programming module
Displaying / modifying control parameters
with Wolf control accessories
* To prevent damage to the boiler TK min must be set > 40 °C