37. Technical information,
air/flue gas routing
Air/flue gas routing
Flue gas routing options
Maximum length
1)
[m]
up to
14 kW
up to
20 kW
up to
24 kW
B23
Flue inside a duct and combustion air directly through the boiler
(open flue)
DN60
DN80
45
-
25
50
21
50
B33
Flue in a duct with horizontal, concentric connection line
(open flue)
DN60
DN80
43
50
23
50
19
50
B33
Connection to a moisture-resistant chimney with
horizontal concentric connection pipe (open flue)
Calculation to EN 13384
(room sealed balanced
flue manufacturer)
C13x Horizontal roof outlet through a pitched roof,
(room sealed - on-site dormer)
DN60/100
DN80/125
10
10
10
10
10
10
C33x
Vertical concentric roof outlet through a pitched or flat roof
Vertical concentric balanced flue for installation in a duct (room sealed)
DN60/100
DN80/125
DN110/160
16
17
18
14
22
25
12
26
30
C43x
Connection to a moisture-resistant balanced flue chimney (room sealed
balanced flue)
Maximum pipe length from the centre of the boiler bend to the connector 2 m
(room sealed)
Calculation to EN 13384
(room sealed balanced
flue manufacturer)
C53
Connection to flue in the duct and ventilation air supply through exterior wall
(room sealed), incl. 3 m ventilation air duct
DN80/125
50
50
50
C53x
Connection to a flue on an external wall (room sealed)
Combustion air intake via external wall
DN80/125
50
50
50
C83x
Connection to flue in a duct and ventilation air through external wall
(room sealed)
DN80/125
50
50
50
C83x Concentric connection to a moisture-resistant chimney
and combustion air through an external wall (room sealed)
Calculation to EN 13384
(room sealed balanced
flue manufacturer)
C93x Flue for installation in a duct
Connecting pipe DN60/100, vertical DN60
rigid
flexible
17
13
17
13
17
13
C93x Flue for installation in a duct
Connecting pipe DN60/100 or DN80/125, vertical DN80
rigid
flexible
18
14
21
17
26
22
1)
The maximum length corresponds to the total length from the appliance to the flue terminal.
For available lifting pressures of gas fans, see specification.
Note: Systems C33x and C83x are also suitable for
installation in garages.
Where necessary, adapt the installation examples to the
relevant building regulations and requirements in your
country/region. Any questions relating to the installation,
particularly regarding the provision of inspection
components and ventilation apertures (ventilation generally
required above 50 kW output) should be raised with your
local flue gas inspector prior to installation.
The specified lengths refer to concentric balanced
flues and standard flues, and apply to original Wolf
components only.
Balanced flue systems DN60/100 and DN80/125
are certified as single units together with Wolf gas
condensing boilers.
The following balanced flues or standard flues with
CE-0036-CPD-9169003 certification may be used:
- Flue pipe DN80
- Concentric balanced flue DN60/100 and DN80/125
- Flue pipe DN110
-
Concentric balanced flue (on external walls) DN80/125
- Flexible flue pipe DN83
Wolf accessories are supplied with the relevant necessary
identification labels.
Please also observe the installation information supplied
with the accessories.