![Wolf CGB-2 Series Installation Instructions For Contractors Download Page 103](http://html.mh-extra.com/html/wolf/cgb-2-series/cgb-2-series_installation-instructions-for-contractors_991733103.webp)
3064810_201804
103
45. Technical parameters according to
EU regulation no. 813/2013
Type
CGB-2-14
CGB-2-20
CGB-2K-20
CGB-2-24
CGB-2K-24
Condensing boiler
[yes/no]
yes
yes
yes
yes
yes
Low temperature boiler (**)
[yes/no]
no
no
no
no
no
B11 boiler
[yes/no]
no
no
no
no
no
Cogeneration space heater
[yes/no]
no
no
no
no
no
If yes, equipped with a supple-
mentary heater
[yes/no]
-
-
-
-
-
Combination heater
[yes/no]
no
no
yes
no
yes
Item
Symbol
Unit
Rated heat output
P
rated
kW
14
19
19
24
24
Useful heat output at rated heat
output and high-temperature
regime (*)
P
4
kW
13.5
18.9
18.9
23.8
23.8
Useful heat output at 30 % of
rated heat output and low-tem-
perature regime (**)
P
1
kW
4.1
5.7
5.7
7.1
7.1
Auxiliary electricity consumption
at full load
elmax
kW
0.025
0.028
0.028
0.029
0.029
Auxiliary electricity consumption
at part load
elmin
kW
0.010
0.012
0.012
0.012
0.012
Auxiliary electricity consumption
in standby mode
P
SB
kW
0.003
0.003
0.003
0.003
0.003
Seasonal space heating energy
efficiency
n
s
%
93
93
93
93
93
Useful efficiency at rated heat
output and high-temperature
regime (*)
n
4
%
88.1
87.8
87.8
87.8
87.8
Useful efficiency at 30 % of
rated heat output and low-tem-
perature regime (**)
n
1
%
98.0
97.7
97.7
97.7
97.7
Standby heat loss
P
stby
kW
0.033
0.033
0.033
0.032
0.032
Ignition burner power consump-
tion
P
ing
kW
0.000
0.000
0.000
0.000
0.000
Emissions of nitrogen oxides
NO
x
mg/kWh
18
17
17
18
18
Declared load profile
(M, L,
XL, XXL)
-
-
-
XL
-
XL
Daily electricity consumption
Qelec
kWh
-
-
0.157
-
0.170
Water heating energy efficiency
nwh
%
-
-
85
-
85
Daily fuel consumption
Qfuel
kWh
-
-
22,878
-
23,006
Contact details
Wolf GmbH, Industriestraße 1, D-84048 Mainburg
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).