![Wolf CGB-2 Series Installation Instructions For Contractors Download Page 67](http://html.mh-extra.com/html/wolf/cgb-2-series/cgb-2-series_installation-instructions-for-contractors_991733067.webp)
3064810_201804
67
34. High efficiency pump function
description
Factory settings for pump speeds
Troubleshooting
Appliance
output
Heating mode
DHW
Standby
heating mode
maximum
minimum
14 kW
70 %
45 %
55 %
30 %
20 kW
70 %
45 %
75 %
30 %
24 kW
70 %
45 %
85 %
30 %
Problem
Remedy
Individual radiators do not warm up
properly.
Carry out hydraulic balancing, i.e.
reduce the flow rate of hotter radiators.
Increase the pump speed (HG16).
In the spring and autumn, the required
room temperature is not achieved.
Increase the set room temperature at
the controller, e.g. with set value setting
± 4.
The required room temperature is not
achieved when outside temperatures
are very low.
Select a steeper heating curve at
the controller, e.g. increase the flow
temperature at standard outside
temperatures.
Summary of Contents for CGB-2 Series
Page 104: ...104 3064810_201804 46 Notes ...
Page 105: ...3064810_201804 105 46 Notes ...
Page 106: ...106 3064810_201804 46 Notes ...