   · Edition 22 July 2020

the alarm code). It is possible to find the last five alarms on the handset shown in the diagnostic menu.

If the handset is available, it is possible to visualize the last occurred alarms (see 

“8.6.1 Consulting the Maintenance Menu with the 

Handset” a pag. 24

.

The following table shows the type of signalling and the relevant alarm detected by the Door Controller:

ALARMS TABLE

Visualized code

Viewed error

Error description

Action undertaken by Door con-

troller

cod. 02

2 flashes

+pause 

Over current protection

Motor over current due to door 

mechanical strain (Note 1)

Auto reset when proper condition 

is restored

cod. 04

4 flashes

+pause 

Power-on motor inverted

Inverted motor connection or 

inverted Encoder channels. Door 

performs a jerk and then stops 

(Note 2)

Auto reset, after about 20 seconds, 

when normal operating conditions 

are restored;  after 5 trials in 5 

minutes the system stops operation 

and waits for external manitenan-

ce.

cod. 05

5 flashes

+pause 

Encoder jerk

Interruption of the motor’s Encoder 

cables, or interruption of the motor 

cables after system’s start up or 

the connecting plug to the Encoder 

motor is inverted

cod. 07

7 flashes

+pause 

Motor jerk

Interruption of the motor cables

cod. 08

8 flashes

+pause 

Over-voltage

Over-voltage in the power supply, it 

works every time the power voltage 

is over circa 50 V.

Auto reset when proper condition is 

restored (Power supply lower than 

45 V.)

cod. 09

9 flashes

+pause 

PWM-Trip

Impulse over-current (shunt short 

circuit)

Auto reset, after about 20 seconds, 

when normal operating conditions 

are restored;  after 5 trials in 5 

minutes the system stops operation 

and waits for external manitenan-

ce.

Notes:

1. 

This alarm indicates an excessive strain on the operator's functioning; it is advisable to check that the system has minimum 

friction, especially during the opening phase.

2. 

If both connections (motor and Encoder signals) are inverted, the door opens when a closing signal is received and closes with an 

opening signal. The Door Operator is pre-wired and tested by the manufacturer; special attention must be taken when replacing 

motor and/or cables.

Summary of Contents for sematic SRS DC-PWM

Page 1: ...ittur com Copyright WITTUR 2020 SRS DC PWM Drive No part of this publication may be reproduced or translated even in part without prior written permission from WITTUR Subject to change without notice...

Page 2: ......

Page 3: ...Instruction with handset 15 6 5 Closing Rest type Instruction with handset 16 6 5 1 Motor on default 16 6 5 2 Motor off 16 6 5 3 PM activation Delay Default 300 sec 16 6 5 4 PM Opening space Default...

Page 4: ...8 5 2 SKATE TYPE select by keypad 23 8 5 4 CLOSING REST TYPE select by keypad 23 8 5 5 MOTOR select by keypad 23 8 5 6 MAX CURRENT END CH select by keypad 23 8 5 7 LA THRESOLD 24 8 6 Maintenance Menu...

Page 5: ...e disclosed to anyone without Sematic s written consent apart from authorized representatives employed by the user which commits itself to the confidentiality clause The Company that makes use of the...

Page 6: ...omatic lift doors Frame and frameless glass doors Enhanced car door operator solutions Complete cabins Car Frames Custom integrated packages Special lift doors cabins and car frames ELEVATOR SYSTEMS S...

Page 7: ...n ensured 1 Quality control of raw material supply 2 Process control 3 Product control 4 Conformity tests according to Sematic specifications Furthermore Sematic guarantees the performance life of its...

Page 8: ...45 plug The handset 7 is a key pad that allows viewing and modification of the function parameters stored in the controller It is important to use the Sematic handset for installation or maintenance a...

Page 9: ...DC PWM Edition 22 July 2020 2 1 SPEED PROFILE 9 Opening cycle O1 Opening low speed O2 Opening hight speed Closing cycle C1 Closing low speed C2 Closing hight speed Key Ka Door opening Kc Door closing...

Page 10: ...60 C HUMIDITY non condensing between 20 and 80 PROTECTION rapid cartridge fuse 5x20 4 A PERFORMANCE SPEED separately adjustable for opening and closing through regulation trimmers REVERSAL SENSITIVIT...

Page 11: ...om Changes can be made without notice PM 2 004922 EN 810 000 000 SRS DC PWM Edition 22 July 2020 4 SIGNALS TO FROM THE DOOR CONTROLLER 4 1 CONNECTIONS 1 Safety chains 2 Main Lift Controller 3 Photocel...

Page 12: ...input signal Voltage from the Main Lift Controller range from 6 to 24 V CC To use this feature Remove the link between terminals 37 38 Connect terminal 37 to the external input signals power source 0V...

Page 13: ...utput signal from a photocell or similar device formed by a voltage free contact so that the door controller will directly receive the command to re open The photocell or similar device has therefore...

Page 14: ...signal loss or failure of the main lift controller the door controller immediately stops the door movement Note in manual mode the main lift controller signals are not active if CLS or OPN switches ar...

Page 15: ...of the doors in low speed forced closing by closing the 15 22 connector pins using a relay voltage free contact 6 3 MOTOR ROTATION DURING CLOSING This function fixes the motor rotation during the clo...

Page 16: ...position error Default 5 mm This sub parameter represents the space threshold with relation to the open skate parking point represented by the PM ACTIVATION DELAY parameter within which the panels can...

Page 17: ...and waits for external manitenan ce cod 05 5 flashes pause Encoder jerk Interruption of the motor s Encoder cables or interruption of the motor cables after system s start up or the connecting plug t...

Page 18: ...losing signal is given for instance after power supply interruption it performs a reset cycle i e it searches for a closing limit at low speed not a self learning cycle 7 2 SELF LEARNING CYCLE PROCEDU...

Page 19: ...speed turn ing it clockwise will set the high closing speed from the minimum speed value to the maximum speed value LW CLS trimmer sets the low closing speed turn ing it clockwise will set the low cl...

Page 20: ...icture 3 a 16 mm diameter hole is required in any chosen position within the Car walls Note when the handset is connected to the controller the display shows the warrantly expiration date 2 years from...

Page 21: ...ittur com Changes can be made without notice PM 2 004922 EN 810 000 000 SRS DC PWM Edition 22 July 2020 8 2 USER HANDSET MENUS AND SUBMENUS Closing Rest type Max current end CL LA Threshold Final low...

Page 22: ...confirm the option On the display the following options are viewed High speed OP XX Low speed OP XX High speed CL XX Low speed CL XX Revers force XX N Acc AP Dec AP Acc CH Acc CH Using keys and to ru...

Page 23: ...osed skate Open skate Using keys and select the required option and press Ok to confirm Keeping the same values on the screen press OK to confirm the following options PM ritardo attivazione PM apertu...

Page 24: ...ave been performed in this working time and the manufacture date The following options are available BACK Press key F1 to restore the menu Maintenance MENU Press key F3 to restore the Main Menu If the...

Page 25: ...available BACK Press key F1 to restore the menu MAINTENANCE MENU Press key F3 to restore the MAIN MENU The access to the MANUFACTURER MENU is reserved protected by password If the option SET FACTORY...

Page 26: ...between handset and controller during the data transfer turn off the controller turn it on again and reconnect the handset The upload starts again from the beginning 10 DOOR OPERATOR MAINTENANCE At le...

Page 27: ......

Page 28: ...YOUR GLOBAL PARTNER FOR COMPONENTS MODULES AND SYSTEMS IN THE ELEVATOR INDUSTRY More information about Wittur Group available on line a WITTUR brand a WITTUR brand a WITTUR brand...

Reviews: