 8.Maintenance and repair 

 

  8.Maintenance and repair 

 

30

 

31

 

 

 

 

3. 

The normal failure and solutions

 

For any malfunctions, please refer to the table below :

 

4. FAQ 

1

 

Why the compressor is not running when I start up the unit?

 

Answer

When the unit is powered on after the last shut-down, the compressor will not run

 

until 3 minutes later. This is the self-protection of the unit.

 

2

 

Why sometimes the outlet water temperature on the display increases slowly?

 

Answer

Because the water temperature is different between the upper layer and bottom

 

layer in the tank at the beginning. When the water temperature in all parts of the tank is

 

basically the same, it will rise faster.

 

3

 

Why the outlet water temperature on the display decreases when the unit is in heating 

mode?

 

Answer

If the upper water temperature is much higher than that of the bottom water, the

 

water temperature will decrease a little because of the convection between hot water and

 

cold water in the tank.

 

4

 

Why does the unit not start up to heat when the outlet water temperature decreases?

 

Answer: 

The water temperature will decrease because of the heat loss if the hot water in the

 

tank is not used for a long time. In order to avoid the continual ON/OFF, the unit does not start 

up until the water temperature decrease for more than 5°C .

 

5

 

Why does the outlet water temperature decrease a lot abruptly?

 

Answer: 

The temperatures of hot water and cold water in the tank are different. The cold

 

water may go to the upper sensor when the hot water have been used up.

 

6

 

Why the hot water is still available when the water out temperature on the display 

decreases a lot?

 

Answer: 

Because the upper sensor is positioned near the top of the tank, there is still 1/5 of hot 

water available when the outlet water temperature on the display decreases a lot.

 

7

 

Why the compressor stops but the fan keeps running when the unit is in the heating

 

mode?

 

Answer: 

The unit needs to defrost when the evaporator freezes because of the low ambient 

temperature. The compressor will stop and the fan keeps running when the unit defrosts.

 

8

 

Why is the heating time so long ?

 

Answer: 

Energy saving, little power consumption and long heating time are the

 

distinguishing features of the units. Normally, the heating time is 2~5 hours according to the inlet 
water temperature, water consumption and ambient temperature.

 

Malfunction

 

Display

 

Canse

 

Solution

 

Bottom water 
temp. Failure

 

P01

 

The water bottom temp. Sensor is 
open or short circuit

 

Check or change the water 
bottom temp. Sensor

 

Top tank water 
temp. Failure

 

P02

 

The water top tank temp. sensor is 
open or short circuit

 

Check or change the water 
top tank temp. Sensor

 

Ambient

 

temp. Failure

 

P04

 

The ambient temp. sensor is 
open or short circuit

 

Check or change the 
ambient temp. 

S

ensor

 

Coil temp. Failure

 

P05

 

The pipe temp. sensor is

 

open or short circuit

 

Check or change the

 

pipe temp. 

S

ensor

 

Refrigerant absorb 
temp. Failure

 

P07

 

The evaporator temp. Sensor

 

is open or short circuit

 

Check or change the

 

evaporator temp. Sensor

 

Anti-freeze temp. Failure

 

P09

 

The anti-freeze temp. Sensor

 

is open or short circuit

 

Check or change the

 

anti-freeze temp. Sensor

 

 

High pressure protection

 

E01

 

The exhaust pressure is high , 

high pressure switch action

 

Check high pressure switch 
and cooling return circuit

 

 

Low pressure protection

 

E02

 

The suction pressure is low, 
Low pressure switch action

 

Check low pressure switch and 
cooling return circuit

 

 

Water flow failure

 

E03

 

No water or litter water 
in water system

 

Check the flow volume ,water 
pump is failure or not

 

Electric-heater

 

overheat protection

 

E04

 

Water flow volume not enough,Water 
system pressure difference is small

 

Check the flow volume,water 
system is jammed or not

 

 

Anti-freeze protection

 

E07

 

Water flow volume not enough,Water 
system pressure difference is small

 

Check the flow volume,water 
system is jammed or not

 

 

Anti-freeze protect level 1

 

E19

 

 

Ambient temperature is too low

 

 

 

Anti-freeze protect level 2

 

E29

 

 

Ambient temperature is too low

 

 

 

Summary of Contents for WSW2.5-300 L

Page 1: ...SANITARY WATER RESERVER Installation Operation Manual WARNING The water heater must be used in reliable ground connection...

Page 2: ...carefully before use the unit All safety measures have safety warnings The followings are the meanings of each warning There will be potential danger for you and others Wrong operations may lead to t...

Page 3: ...more than 50 C please have a qualified socket to replace it to avoid the burnout or fire caused by the bad contact In the water splashed places and may be on the wall the installation height of power...

Page 4: ...e risk or serious injure ATTENTION There will be potential danger for you and others Icon Meaning Prohibition What is prohibited will be nearby this icon Compulsory implement The listed action need to...

Page 5: ...ll lead to water leakage electrical shock or fire Choose the place that there are no direct sunlight and other heat radiating If you can not avoid it please install coverings to prevent the direct sun...

Page 6: ...withsimpleoperationbutalsocouldsetthewatertemperatureaccordingtotheambient temperature heating the water meanwhile recycling indoor waste heat Refrigerant is compressed into vapor with high temperatur...

Page 7: ...rating parameters The range of the operating water temperatures 9 70 C The range of the operating water pressures 0 15 0 7MPa Solar water outlet Drainage Water inlet A B C 116 244 800 Model WSW2 5 300...

Page 8: ...erent needs and conditions Solar water inlet Water source 600 500 The unit only can use tap water Please do not use the water from any lake river or underground water which are not filtrated or treate...

Page 9: ...ht of forklift at a lowest level Because the top part is heavier the operator needs to take measures to prevent its overturn To avoid any damages the unit must stand on a flat place Transport for inst...

Page 10: ...hould be clean no rusty spots and dirts to avoid any pipe jam After connecting pipes please check the leakage status of whole system to assure there is no leakage firstly and then make the insulation...

Page 11: ...controller to see if there is any malfunction Trial running Use the wire controller to start the unit When compressor is running hear whether there is strange sound or not If abnormal sound occurs ple...

Page 12: ...It is showed when unit is in auto mode Heating It is showed when unit is in heating mode Vacation mode It is showed when unit is in vacation mode Off peak mode It is showed when unit is in off peak m...

Page 13: ...economic mode for a certain period and run in high requirement mode for the others Automatic heating mode the unit will change its mode according to the ambient temperature Vacation mode the unit wil...

Page 14: ...ss to save setting At the same time month start to flashing press to increase value or press to decrease value and press to save setting At the same time year start to flashing press press to increase...

Page 15: ...n the following Attention If there is no operation for 5s system will remember clock setting and back to the main interface Timer 1 off has been set 2 The timer on off setting operation at vacation mo...

Page 16: ...when the outlet temperature reaches target temperature system will shut down electric heater automatically It is used for high requirement When the unit is off you can start up electric heater only by...

Page 17: ...7 Operation and Usage 7 Operation and Usage 26 27 Set point of target temp 55 C Ajustable...

Page 18: ...ure below and clean it with tap water Loosen the two screws in the top of the water heater indicated in the picture blow to remove the front panel and wire controller Squeeze and pull out the filter F...

Page 19: ...ing mode Answer The unit needs to defrost when the evaporator freezes because of the low ambient temperature The compressor will stop and the fan keeps running when the unit defrosts 8 Why is the heat...

Page 20: ...taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directiv...