background image

13

OPM-151/A

YOURGEN 

The WINCO YourGen meter allows 

you to see useful information about 

your generator from the front panel by 

displaying RPMs, Voltage, frequency, 

load, hours, and maintenance reminders. 

It also has the ability to display warnings 

if any parameter gets outside of normal 

operation range. 

Cycle Button (      ) -

During normal operation, the display will toggle through 

on fixed delay. If you want to see any specific item, you 

can press the cycle button to move it to that setting. Once 

the display is selected, the delay before it starts toggling is 

approximately 5 seconds. This button is also used to reset 

maintenance reminders.

RPM - 

The meter will display the RPMs of the engine. This number 

is calculated based upon frequency and is not directly 

measured from the engine. The engine-generator must be 

run at the correct speed in order to produce the proper 

electrical voltage and frequency.

CAUTION: EQUIPMENT DAMAGE

The output voltage should be checked to ensure the 

generator is working properly prior to connecting a 

load to the generator. Failure to do so could result 

in damage to equipment plugged into the unit and 

possible injury to the individual.

Operating Speed: All engines have a tendency to slow 

down when a load is applied. When the electrical load is 

connected to the generator, the engine is more heavily 

loaded, and as a result, the speed drops slightly. This slight 

decrease in speed, together with the voltage drop  within 

the generator itself, results in a slightly lower voltage 

when the generator is loaded to its full capacity than 

when running no load. The slight variation in speed also 

affects the frequency of the output current. This frequency 

variation has no appreciable effect in the operation of 

motors, lights, and most appliances. However, electronic 

equipment and clocks will be affected if correct RPM is not 

maintained. See Load vs. Output chart.

Although individual units and models vary slightly, the 

normal voltage and frequency of the engine-generator 

described in this manual are approximately as follows, 

under varying loads:

LOAD vs. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

120V 

Recpt

240V 

Recpt

None

3600

60.0

120V

240V

Half

3600

60.0

120V

240V

Full

3510

58.5

120V

240V

The speed of the engine was carefully adjusted at the 

factory so that the generator produces the proper voltage 

and frequency. For normal usage, the speed setting should 

not be changed. If the generator is being run continuously 

on a very light load, it is often advisable to lower the 

operating speed slightly. 

The engine will govern itself at full speed. Intentionally 

overriding the governor and operating the generator at 

low voltage may damage both the generator and any load 

connected to it. Running the engine at excessively high 

speeds results in high voltage, which may significantly 

shorten the life of light bulbs and appliances being used, as 

well as possibly damaging the engine.

CAUTION: EQUIPMENT DAMAGE

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY 

A QUALIFIED SERVICE TECH. Whenever making any 

speed adjustments, check the YourGen meter and be 

sure the voltage and speed are correct.

Output voltage should be checked periodically to ensure 

continued proper operation of the generating plant and 

appliances. 

Hz -

This is the measured frequency of the generator set. See 

the table in the RPM section above for an explanation of 

voltage and frequency ranges under load.

V1 - 

Output voltage of Line 1 (L1 on panel) to neutral. See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

V2 - 

Output voltage of Line 2 (L2 on panel) to neutral. See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

V1-V2 -

Output voltage of Line 1 (L1) and Line 2 (L2). See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

Hours -

This displays the total running hours of the generator set. 

When the generator is turned off, the hours will remain 

displayed. The display is run on a CR2032, ten-year battery. 

Once the unit is running, the battery connected to the unit 

will then supply the power to the YourGen meter.

Load Bars - 

These bars indicate how much load is being used on Line 1 

(L1) and Line 2 (L2).

   

= 1-25%             = 25-50%             = 50-75%              = 75-100%

It is good practice to monitor the YourGen Meter when 

applying load. This will ensure the generator is balanced. 

 

 

 

Balanced                        Unbalanced

Summary of Contents for WL16000HE-03/A

Page 1: ...ontact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE _________________________________________ DEALER NAME ___________________________________________ DEALER PHONE ________________________________________ www wincogen com 16200 031 ...

Page 2: ...LEANING TROUBLESHOOTING TABLE 18 WIRING DIAGRAM 19 CA EVAPORATIVE EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator Read and understand all instructions in the manual before starting and operating the generator Keep this manual available for future reference USING ...

Page 3: ...t must be mixed with fresh air A Operate only in well ventilated areas B Never operate indoors including attached garages C Never operate the unit in such a way as to allow exhaust gases to seep back into closed rooms i e through windows walls floors WARNING FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B K...

Page 4: ... low variable load Derate the running watts 20 for these types of loads GENERATOR Generator Manufacturer Mecc Alte Spa Generator Model Number S20FS 230 A Part Number 16428 002 Rotor Resistance 8 04 Ohms Stator Resistance 0 056 Ohms Excitation 0 41 Ohms Capacitors 31 5 µF qty 1 35 µF qty 2 Capacitor Part Number 300323 112 31 5 µF 300323 212 35 µF ENGINE Engine Manufacturer Honda Engine Model Number...

Page 5: ...te performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle assembly may cause excessive vibration and damage to the engine generator set DO NOT operate and or store the unit outside during inclement weather without adequate protection from the elements Failure t...

Page 6: ...ame amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard starting load such as an air compressor it will require more starting current If it is connected to a light load or no load such as a power saw it will require less starting current The exact requirement will also vary with the brand or design ...

Page 7: ...el surface before you check or add oil to the system The necessity of using the correct oil and keeping the crankcase full cannot be overemphasized Engine failures resulting from inadequate or improper lubricant are considered abuse and not covered by the generator or engine manufacturer s warranty OIL RECOMMENDATIONS Outdoor temperatures determine the proper oil viscosity for the engines Winco re...

Page 8: ...t engines are NEGATIVE GROUND Use extreme caution when connecting the battery Connect the NEGATIVE battery terminal to GROUND For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the Bat terminal Make sure all connections are clean an tight Reverse the sequence when disconnecting disconnect the negative cable first These eng...

Page 9: ...utes If the choke knob was pulled to the CLOSED position to start the engine gradually push it to the OPEN position as the engine warms up To stop the engine in an emergency simply turn the engine switch to the OFF position Under normal conditions use the following procedure Refer to the instructions provided by the equipment manufacturer Move the throttle lever to the MIN position Some engine app...

Page 10: ...s Sta Bil or equivalent will minimize the formation of gum deposits during storage The additive may be added to gasoline in the engines fuel tank or to gasoline in a storage container A Add the fuel stabilizer to the fuel in the tank and run for 2 minutes to circulate the stabilizer throughout the fuel system B If you choose to remove the remaining fuel from the fuel tank it must be drained into a...

Page 11: ...references STANDARD PORTABLE GENERATOR Your WINCO portable generator ships with a bonded neutral You can safely use this generator without external grounding as long as all loads are powered through the receptacle panel VEHICLE MOUNTED GENERATOR Your WINCO portable generator ships with a bonded neutral When mounted to a vehicle to safely distribute power it is necessary that the generator frame is...

Page 12: ...bution panel must be installed by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in mind only a limited amount of amperage is available from the generator set Some circuit breakers may still have to be turned off to prevent an overload on the generator during the initial start up S...

Page 13: ...UT Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3600 60 0 120V 240V Half 3600 60 0 120V 240V Full 3510 58 5 120V 240V The speed of the engine was carefully adjusted at the factory so that the generator produces the proper voltage and frequency For normal usage the speed setting should not be changed If the generator is being run continuously on a very light load it is o...

Page 14: ...r will light up the oil icon and the word change will flash Once the oil has been changed press and hold the cycle button for approximately 5 seconds until the warning has been removed from the display to reset the warning The meter will then remind you of oil changes on the appropriate schedule for your generator It is important to remember that the engine manufacturer recommends changing the oil...

Page 15: ...he gasket contacts the oil filter adapter then tighten the oil filter 1 2 to 3 4 turns F Replace oil drain bolt making sure the sealing washer is in place G Remove the oil filler cap and refill with new oil Make sure to use the proper grade oil based on your operating temperature NOTE This engine requires 57 6 ounces 1 8 quarts of oil if it is completely drained Use caution when refilling the engi...

Page 16: ... damage the engine Replace annually or every 300 hours of operation Always replace with the same spark plug that came in the engine and check gap before installing Spark plug gap is 0 030 Poor spark will also occur if spark plug wire does not fit ENGLISH Inspection Cleaning CKET AIR CLEANER COVER LATCH AIR CLEANER CASE PACKING FOAM FILTER ELEMENT PAPER FILTER ELEMENT AIR CLEANER COVER WING NUT AIR...

Page 17: ...B Receptacles Quality receptacles have been utilized If a receptacle should become cracked or otherwise damaged replace it Using damaged or cracked receptacles can be both dangerous to the operator and destructive to the equipment CLEANING Remove dirt and debris with a cloth or brush CAUTION EQUIPMENT DAMAGE DO NOT use high pressure spray to clean either the engine or the generator The high pressu...

Page 18: ...efective load Defective receptacle Excessive load Voltage too high Engine speed is too high Generator overheating Overloaded Insufficient ventilation No output voltage Short in load disconnect Tripped or defective circuit breaker Broken or loose wire Defective receptacle No residual magnetism in generator Defective stator Defective rotor field Shorted capacitor Shorted diodes on rotor GFCI recepta...

Page 19: ...19 OPM 151 A WIRING DIAGRAM GND GND GND GND GND GND N N N N N N N G3 G3 G3 G3 G3 G3 G3 G3 G3 G3 G1 G1 G1 G1 G1 G1 G1 G1 G1 G1 G1 G1 ...

Page 20: ...and Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use and service will be repaired or replaced For warranty service return the product within the warranty period to your nearest WINCO Authorized Service Center or to WINCO in Le Center Minnesota Duration...

Reviews: