background image

WINCO INC. 225 S. CORDOVA AVE. LE CENTER, MN  56057 

SERVICE DEPT. 507-357-6831 • SALES DEPT. 507-357-6821

www.wincogen.com

INSTALLATION AND 

OPERATORS

RP25/D

GENERATORS

MANUAL

DSE 7310 MKII ELECTRIC START

Summary of Contents for RP25/D

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 SERVICE DEPT 507 357 6831 SALES DEPT 507 357 6821 www wincogen com INSTALLATION AND OPERATORS RP25 D GENERATORS MANUAL DSE 7310 MKII ELECTRIC START...

Page 2: ...SWITCH ELECTRICAL CONNECTIONS 10 RECEPTACLE PANEL A C ELECTRICAL CONNECTIONS GROUNDING CAM LOCK CONNECTIONS D C ELECTRICAL CONNECTIONS STARTING PROCEDURE 12 SELECTING THE CORRECT VOLTAGE DC INTERCONN...

Page 3: ...erial number as yours If you should ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ________...

Page 4: ...rmance Poor maintenance improper or careless use can result in potentially deadly hazards from electrical shock exhaust gas asphyxiation or fire Please read all safety instructions carefully before in...

Page 5: ...1 8 Gal Hr Engine Fluid Specifications Fuel ASTM D 975 1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 8 6 Quarts Cooling System 50 50 mix GENERATOR END NOTE Review the Sta...

Page 6: ...onsists of a multi cylinder liquid cooled engine nominally operating at 1800 rpm The generator frequency regulation is maintained by the engine governor to within 1 5 Hz cps from no load to rated load...

Page 7: ...er emphasized Failure to use the proper oil and keep the crankcase properly filled will cause excessive engine wear and shorten its useful life PREPARING THE UNIT UNPACKING 1 As you receive your unit...

Page 8: ...onnect the battery negative cable When removing the battery cables from the battery reverse the procedure disconnect the negative first and then the positive cable 5 Be sure all connections are tight...

Page 9: ...second start delay and a 15 second transfer delay to allow the engine to warm up before transferring the load to the generator When the line power is restored the ATS has a 5 minute transfer delay to...

Page 10: ...it THIS RECEPTACLE UTILIZES A HUBBLL PLUG PART CS6365 K 250V 50 AMP CIRCUIT BREAKERS These circuit breakers protect the 2 50 amp twistlock receptacles H L 120V 20 AMP CIRCUIT BREAKERS These two push b...

Page 11: ...engine generator set and the generator set must be properly grounded to good earth ground Generally an 8 foot copper rod driven into the earth will provide a proper earth ground GROUND NEUTRAL L1 L2...

Page 12: ...n the display SELECTING THE CORRECT VOLTAGE A variety of phase voltages are available from the four position selector switch The four basic connection patterns are Delta 120 240 Low or Parallel Wye 12...

Page 13: ...connected can cause serious personal injury or equipment damage DO NOT jump start these engine generator sets Starting these units on a low battery or jump starting them will cause damage to the engi...

Page 14: ...ext to the AUTO button NOTE For setting the exerciser circuit for all ATS see the operator s manual shipped with the ATS WARNING EQUIPMENT DAMAGE Never apply a load to the generator until you have fir...

Page 15: ...e Cam Locks If you need to run an isolated neutral system the jumper between the neutral and ground musts be removed at the terminal block 4 Grounding The Unit To comply with current safety standards...

Page 16: ...the DSE 7310 MKII Normally it will tell why the unit has failed This will shorten your trouble shooting time and in many cases prevent the replacement of parts that may not be defective Problem Possib...

Page 17: ...HHN THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 2...

Page 18: ...18 OPM 114 REV B SELECTOR SWITCH WIRING DIAGRAM SEE FOLLOWING PAGE FOR REFENCES...

Page 19: ...5 6 7 5 9 6 216 5 9 51 6 5 37 21 7 33 1 8 21 5 56 5 6 7 87 67 6 6 7 6 1 6 6 7 6 1 0 5 029 5 1 8 6 1 83 7 1 8 5 6 00 5 2 6 6 7 00 5 9 5 286 1 335 7 7 92 7 6 725 6 7 66 0 7 7 7 5 1 02 3 57 5 7 6 5 1 217...

Page 20: ...20 OPM 114 REV B DSE 7310 MKII WIRING DIAGRAM...

Page 21: ...PHASE AC WIRING HIGH AND LOW WYE THREE PHASE L 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS 24 5060 00 60708 165 REE PHASE AC WIRING H AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS SE HIGH WYE TS...

Page 22: ...GLE PHASE 240 VOLTS G 4 LEAD THREE PHASE WIRING DELTA THREE PHASE DELTA 120 240V SINGLE PHASE AC WIRING 4 LEAD 5060 00 60708 165 THREE PHASE DELTA 120 240 VOLTS THREE PHAS WIRING DE SINGLE PHASE 120...

Page 23: ...1 725 1 1 51 66 211 725 8 7 7 21 2 22 17 2 3 8 6 1 725 2 3 8 5 67 57 62 12 3 27 5 5 5 9 6 216 5 9 51 6 5 37 21 7 33 6HH 6KHHW 56 5 61 6 6 7 6 1 6 6 76 6 1 6 6 7 6 6 7 1 335 7 7 1 1 51 66 7 7 7 5 1 02...

Page 24: ...d fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some st...