background image

9

3180-10

60706-238

WARNING: PERSONAL INJURY

    Lead acid batteries produce explosive hydrogen 
gas when charging.  Keep sparks, fl ames, and 
burning cigarettes away from the battery.  Ventilate 
the area when charging or using the battery in an 
enclosed space.  Lead acid batteries contain sulfuric 
acid, which causes severe burns.  If acid contacts 
eyes, skin or clothing, fl ush well with water.  For con-
tact with eyes, get immediate medical attention.

BATTERY CHARGING

Units equipped with electric start have a small fl y-
wheel charger built into the engine fl ywheel assem-
bly for recharging the starting battery.  This fl ywheel 
charger generates a small AC current that passes 
through a diode assembly to produce a DC charg-
ing current of about 1 to 3 AMPS.  This circuit is not 
designed to be used as a battery charging circuit to 
recharge dead batteries.

OPTIONAL DOLLY KIT

An optional dolly kit is available for this generator.  
The dolly kit comes with instructions and parts list.  
After installing the dolly kit, fi le the instructions and 
parts list in the back of this manual for future refer-
ence.

OIL ALERT SYSTEM

This WINCO generator is equipped with a low oil 
shutdown system.  This engine uses an fl oat switch 
mounted inside the engine. If the oil level drops 
below a certain point the low oil module on the 
engine will shut it down. This low oil warning system 
will automatically stop the engine before the oil level 
reaches a critical danger point.  This feature is de-
signed to prevent costly repairs  and downtime.

CAUTION: EQUIPMENT DAMAGE

    Allowing the engine to shutdown repeatedly on 
low oil level may cause excessive wear which can 
be cumulative.

INITIAL START UP

The throttle control on these generators is preset and 
locked to operate at 3600 RPM (nominal) with no load 
speed set at 3690 RPM.  Only a trained service tech-
nician should be allowed to adjust this speed setting.  

NOTICE:  ENGINE START LOCKOUT

    

This unit will not start if it is low on oil.  The lu-

bricating oil level must be at the full mark before the 
engine will start and run.

BASIC OPERATION

MANUAL STARTING (Gasoline Only)

Refer to the engine manual for additional starting, 
operating, and stopping instructions.

1.  Check oil level. Refi ll as needed.
2.  Turn on the fuel supply by moving the fuel lever  
 

to the “ON” position. 

NOTE

 - There is a second fuel valve under the fuel 

tank that is used when removing the tank.  This valve 
is normally left on.
3.  Move the choke lever to the “CLOSED” position.  
 

To restart a warm engine, leave the choke lever in  

 

the “OPEN” position

OFF

O

O

N

N

MAX.

MIN.

OPEN

OPEN

FUEL VALVE LEVER

O

O

N

N

CLOSED

MIN.

ON

MAX.

MIN.

OPEN

CLOSED

O

O

P

P

E

E

N

N

ON

C

C

L

L

O

O

S

S

E

E

D

D

CHOKE LEVER

MIN.

Summary of Contents for Home power HPS6000HE

Page 1: ...INSTALLATION AND OPERATORS MANUAL HPS6000HE I BI FUEL GENERATOR...

Page 2: ...ion 8 INITIAL START UP Basic Operation 9 Manual Starting Gasoline only 9 Electric Starting Gasoline 10 Electric Starting NG 11 Stopping Storage 11 Operating Speed 12 CONNECTING THE LOADS 12 Wiring 13...

Page 3: ...dren c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel on...

Page 4: ...making enclosures for generators that have been properly engineered The use of these 3rd party enclosures is acceptable as long as they have been certified and meet current code DO NOT attempt to ope...

Page 5: ...otify the trans portation company immediately request proper pro cedures for filing a concealed damage claim Title to the equipment and responsibility for filing a claim rests with you when a generato...

Page 6: ...upplier The fuel source should be as close as possible to the outdoor operating location This will reduce the installation cost of fuel runs Connect the fuel supply line to the inlet of the fuel deman...

Page 7: ...te Length of Fuel Line Fuel Line Size less than 50 feet 3 4 inch black pipe 50 to 200 feet 1 inch black pipe Allow an additional 3 feet for each standard elbow Do not use street ells restrictive Consu...

Page 8: ...he unit If you intend to use the power plant s electric start system required when using NG you will need to purchase and install a battery to operate it Units equipped with a recoil or rope start wil...

Page 9: ...de the engine If the oil level drops below a certain point the low oil module on the engine will shut it down This low oil warning system will automatically stop the engine before the oil level reache...

Page 10: ...the fuel supply by moving the fuel lever to the ON position 3 Move the choke lever to the CLOSED position To restart a warm engine leave the choke lever in the OPEN position 4 Turn the engine switch...

Page 11: ...mer blended gasoline Using gasoline left over from winter may cause the unit to vapor lock STOPPING AND STORAGE 1 Move the engine switch to the OFF position 2 Turn off the fuel supply valve 3 Before e...

Page 12: ...oltmeter and a frequency meter or tachometer and be sure the voltage and speed are correct Lower voltage may damage both the generator and any load connected to it Running the engine at ex cessively h...

Page 13: ...receptacle on these units are designed to power both 120 or 240 volt loads The plug for this receptacle can be wired for either 120 volt 240 volt or a combination of 120 and 240 volt loads depending...

Page 14: ...nually or every 100 hours Service more often under dusty conditions WARNING EQUIPMENT DAMAGE Never start or run the engine with the air filter re moved a Remove the wing nut from the air cleaner cover...

Page 15: ...alified electrical service technician USE ONLY FACTORY APPROVED REPAIR PARTS a Bearing The bearing used in these generators is a heavy duty double sealed ball bearing They require no maintenance or lu...

Page 16: ...o output voltage Short in load disconnect Tripped or defective circuit breaker Broken or loose wire Defective receptacle No residual magnetism in generator Defective stator Defective rotor field Short...

Page 17: ...17 3180 10 60706 238 WIRING DIAGRAM...