  spin backwards possibly damaging them.

NOTICE:

If for any reason during the check out procedure the 

voltage and frequency are not correct, depress the STOP/

RESET button and correct the trouble before proceeding.

4. Stopping - There are two ways to stop the unit when it is 

  in the manual mode. Pressing the STOP/RESET button will 

  stop the unit immediately. Pressing the AUTO mode 

  button will stop the unit but only after the cool down 

  timers have timed out and there is no remote start signal 

  being sent to the unit.

WARNING: EQUIPMENT DAMAGE

Always make sure the generator runs under no load for 

five minutes before stopping to allow the engine and 

components to cool down. Don’t use the E-Stop as the 

standard.

AUTO MODE

To activate the automatic start mode you will just need to 

depress the AUTO button, the LED indicator beside the 

button confirms that the unit is in automatic mode.

To test the Automatic Transfer Switch, follow the instruction 

on the operator’s manual that came with the transfer 

switch. If you get a fault during the initial start up or prior 

to start up, it is most likely a false warning light. Simply reset 

the ATS to start over.

Once you have completed testing of the ATS, be sure you 

ALWAYS leave the system in the standby mode,unless 

servicing the unit. For standby operation, press the AUTO 

button on the front of the control. The green light should 

light up next to the AUTO button.

NOTE: For setting the exerciser circuit, for all ATS, see the 

operator’s manual shipped with the ATS. 

CONTROL POWER

The DSE7310 controller consumes small amounts of battery 

power when it is in use. The controller comes with a power 

switch that disconnects battery power when it is not in use. 

The switch is designed with a safety relay that prevents it 

from removing power to the controller while the generator 

is operating. If the switch is turned off while the engine is 

running it will continue operating until the engine shuts 

down and then the controller will power down. 

This switch should be used when the generator is not 

going to be used over the course of several days and the 

generator is not connected to a battery charger. 

A solar charger kit is the easiest way to always maintain the 

battery during storage in mobile applications. The supplied 

battery charger can be plugged in to an extension cord on 

mobile applications.

Summary of Contents for DR12I4-03

Page 1: ...ed to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE...

Page 2: ...R CHANGING AIR FILTER DRAINING WATER SEPARATOR CLEANING WATER SEPARATOR ADJUSTING THE GOVERNOR STORAGE RETURNING ENGINE TO SERVICE MAINTENANCE SCHEDULE TROUBLE SHOOTING TABLES 23 WIRING SIZE TABLE 24...

Page 3: ...e explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator set or fuel tank D Keep a...

Page 4: ...16 Hertz 60 60 60 60 ENGINE Model ISUZU 3CE1 Starting System 12 Volt Fuel ASTM D 975 1D OR 2D Oil Type See Lubrication section in this manual Oil Capacity 7 Quarts Cooling System 50 50 mix See engine...

Page 5: ...y records Several of the major components also have their own individual data plates providing additional information to document build data for warranty and replacements parts Be sure to have the mai...

Page 6: ...olts 4 Unit can now be lifted from shipping rails LIFTING THE GENERATOR SET NOTICE PERSONAL INJURY To prevent injury to persons or equipment observe the following guidelines when lifting the generator...

Page 7: ...to a solid base The engine generator is mounted on channels which are attached with special shock mounts to the main frame This allows the engine generator free movement without affecting the base or...

Page 8: ...potential for contact with people is controlled Exhaust can enter buildings through windows ventilation systems and other openings if proper precautions are not followed The exhaust must be isolated...

Page 9: ...Remove watches rings and other metal objects 2 Use tools with insulated handles 3 Check both the battery cable ends and the battery posts to be sure they are free of corrosion 4 Always connect the bat...

Page 10: ...recharge the battery before attempting to start the unit Boost jump starting this unit improperly will result in PERMANENT DAMAGE TO THE ENGINE CONTROL MODULE ECM BATTERY CHARGER BLOCK HEATER BATTERY...

Page 11: ...to 200 in lbs D 120V GFCI CIRCUIT TERMINAL BLOCK These terminals are rated for 20 Amps and will handle wire sizes 4 AWG to 18AWG They should be torqued to 16 in lbs This circuit must be fed from a fus...

Page 12: ...5 The ports are wired onto the back of the DSE7310 In order to finalize communication the program will need to be adjusted using the free DSE configuration software to enable the commutation Contact W...

Page 13: ...SCO 300 UL SWITCH When Normal Source Fails Terminals On Transfer Switch Contact Closes TB1 and TB2 Contact Opens TB1 and TB3 Engine start and auxiliary circuit terminal block TB located on 3ATS 3NTS t...

Page 14: ...il and keeping the crankcase full cannot be over emphasized Failure to use the proper oil and keep the crankcase properly filled will cause excessive engine wear and shorten its useful life WINCO reco...

Page 15: ...The small LED light next to it should come on Note There is no start delay in this mode of operation 2 Press and release the green START ENGINE button The DSE 7310 will send two signals to the engine...

Page 16: ...start up it is most likely a false warning light Simply reset the ATS to start over Once you have completed testing of the ATS be sure you ALWAYS leave the system in the standby mode unless servicing...

Page 17: ...be changed VOLTS To adjust generator output voltage Clockwise to increase voltage STABILITY To prevent voltage hunting Clockwise to increase the dampening effect UFRO Under Frequency Roll Off Termina...

Page 18: ...als on lubricant and filter changes may need to be shortened An oil quality testing program can also provide early warnings or oil degradation Efforts may need to be made to reduce the amount of dust...

Page 19: ...drained close the valve 5 Top off through the filler port using lubricant oil with the suitable oil table in the LUBRICATION section of this manual 6 Use the dip stick to ensure the level of oil does...

Page 20: ...aminants Then reinstall and tighten the drain plug or close the drain valve in the radiator Reinstall and tighten the engine block drain plug 5 Fill radiator and engine with engine coolant CLEANING RA...

Page 21: ...4 Replace the element with a new one if the element is damaged excessively dirty or oily 5 Clean inside of the air cleaner cover 6 Reinstall the element into the air cleaner case 4 Note If there is a...

Page 22: ...e leaving the fuel system shut off so the engine will not start for 15 seconds Then pause for 30 seconds Repeat the procedure until you have cranked the engine for a total of one minute This will circ...

Page 23: ...fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water temper...

Page 24: ...THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 50 65 85 100 115 130 150 175 200 230...

Page 25: ...725 127 620 02 6 20 48 3 7 8 9 2 35 6685 1 22 17 7 03 5 785 6 7 6 6 1 5 81 76 3 785 8 1 2 22 17 021 725 1 785 6 5 237 21 27 1 8 62 12 7 1250 26 9 9 5 9 6 216 5 9 51 6 5 37 21 7 33 3 25 1 7 2 5 3 83 7...

Page 26: ...5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 56 6 2 1 29...

Page 27: ...27 OPM 145 D THREE PHASE AC WIRE HIGH AND LOW WYE THREE PHASE AC WIRING DELTA SINGLE PHASE 311 WINDING WIRING DIAGRAMS...

Page 28: ...d liable for any special indirect consequential or liquidated damages WINCO Inc shall not be liable for any claim that requires replacement of engine part or component of the product that is no longer...

Reviews: