background image

 

            

  8 Circuits Generator Interlock Kit: THQLLX8CU

 
 
 

General 

To  comply  with  the  National  Electrical  Code  and 
Underwriters  Laboratories,  the  Generator  Interlock  kit 
must  be  installed  in  accordance  with  the  information 
contained  in  this  instruction  manual  and  by  a  qualified 
electrical contractor and/or licensed electrician. 

 

Introduction 

This  bulletin  provides  instructions  for  installing  the 
interlock  and  circuit  breaker  retainer  on  the  150-200A 
rated  8  Circuits  Interior  GE  Meter  Socket  Load  Centers: 
TSM815CSCU, 

TSM820CSCU, 

TSMF815CSCU, 

and 

TSMF820CSCU. 

 

Installation 

Step 1: Drill the Mounting Holes on Dead front 

A drilling template is provided to ensure proper alignment 
of the interlock 

1.

 

Make  sure  that  the  four  0.5”  knockouts  below  the  4-
pole main breaker have been removed.

 

2.

 

Insert  the  folds  of  the  template  in  the  knockouts 
mentioned  above  and  slide  towards  the  4-pole  main 
breaker  outer  surface  until  it  ceases  to  slide  further 
(see Figure 1).

 

3.

 

Drill the pilot holes through the two identified holes in 
the template using a 3/32” (0.093”) drill bit.

 

4.

 

Remove the drill template.  

5.

 

Uninstall  the  dead  front,  and  retain  the  mounting 
screws. 

6.

 

Re-drill the two pilot holes with ¼” (0.250”) drill bit. 

7.

 

Remove any burrs resulting from drilling the holes

 

.

  

 
 
 
 
 

 

 

 

Figure  1:  Mounting  Hole  Template 

 

Step 2: Install the Retainer 

1.

 

Uninstall  and  discard  the  existing  main  breaker 
retainer, and retain the mounting screws.

 

2.

 

Install  the  2-pole  back-fed  main  breaker  in  the 
position shown in Figure 2.

 

3.

 

Install  the  conductors  into  the  2-pole  back-fed  main 
breaker. Check breaker for wire range and tightening 
torque information.

  

4.

 

Install the retainer and secure using the nuts provided 
in the kit (see Figure 1). Tighten to 35 lbs-in (4 N-m).

 

 

 

Figure  2:  Main  Breaker  Retainer 

 

4-Pole 
Main Breaker

Back-fed 
Main Breaker

Interior

Mounting 
Screws

Retainer

4-Pole 
Main Breaker

Back-fed 
Main Breaker

Interior

Mounting 
Screws

Retainer

DEH 41152 Generator Interlock Kit Installation Instructions    R03 

WARNING

: Hazard of electrical shock or burn 

Turn off power supplying this equipment before working inside 

GE Energy 

Reviews: