13

OPM-103

REV B

the allowable level the Safety Latching Relay button will pop out and 

the unit will shutdown. You will also get a check engine light at this 

time. If you find the unit stopped with the relay button popped out, 

it could have been caused by either low oil pressure or high water 

temperature.

DSE4510 ENGINE CONTROLLER

STOP/RESET (red button) - This button places the 

module into its Stop/Reset mode. This will clear any 

alarm conditions for which the triggering criteria have 

been removed. The fuel supply de-energizes and the 

engine comes to a standstill. Should a remote start 

signal be present while operating in this mode, a 

remote start WILL NOT occur.
AUTO (white button) - This button places the module 

into its Automatic mode. This mode allows the module 

to control the function of the generator automatically. 

The module will monitor the remote start input 

and once a start request is made, the set will be 

automatically started and placed on load. The module  

will then wait until the next start event.

START (green button) - Pressing this button from 

STOP/RESET will start the engine and run the load. 

MENU NAVIGATION - Used for navigating the 

instrumentation, event log, and configuration screens. 

PROTECTIONS

When an alarm is present, the common alarm LED if configures will 

illuminate. The LCD display will show an icon to indicate the failure.

WARNINGS

Warnings are non-critical alarm conditions and do not affect the 

operation of the generator system, they serve to draw the operator’s 

attention to an undisirable condition. Warning alarms are self-resetting 

when the fault condition is removed. The icon will appear steady in they 

display.

SHUTDOWN

Shutdowns are critical alarm conditions that stop the engine and draw 

the operator’s attention to an undesirable condition. Shutdown alarms 

are latching. The fault must be removed and the STOP/RESET button 

pressed to reset the module. The icon will appear flashing in the 

display.

MODULE DISPLAY

FRONT PANEL CONFIGURATION

  1. Press the        and the       buttons together to enter the editor             

                mode.

  2. Press the         or        navigation buttons to cycle through the front 

        panel editor to select the required page in the configuration tables.

  3. Press the        to select the next parameter or         to select the 

      previous parameter within the current page.

  4. When viewing the parameter to be edited, press the         button, 

         the value begins to flash.

  5. Press the        or        buttons to adjust the value to the required 

      setting.

  6. Press the        button to save the current value, the value ceases 

      flashing.

  7. Press the

        button to save and exit the editor, the configuration 

      icon         is removed from the display.

NOTES:

Pressing ans holding the

        or

        buttons will give auto-repeat 

functionality. Values can be changed quickly by holding the 

buttons for a prolonged period of time.

The editor automatically exits after 5 minutes of inactivity to 

ensure security.

The PIN number is not set by WINCO when the module leaves the 

factory. If the code has been ‘lost’ or ‘forgotten’, the module must 

be returned to the DSE factory to have the module removed. A 

charge will be made for this procedure.

NB - This procedure cannot be performed away from the factory.

The PIN number is automatically reset when the editor is exited 

(manually or automatically) to ensure security.

Example of DSE home page display

Summary of Contents for DE SERIES

Page 1: ...INCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS DE SERIES GENERATORS MANUAL MANUAL KEY START AND DSE4510 ELECTRIC START...

Page 2: ...lected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is important that you carefull...

Page 3: ...oper instruction B Guard against electric shock C Avoid contact with live terminals or receptacles D Use extreme care if operating this unit in rain or snow E Use only three prong grounded plugs and e...

Page 4: ...ations Oil Type See Lubrication section in this manual Oil Capacity 8 6 Quarts Cooling System 50 50 mix SPECIFICATIONS DE20I4 MODEL DE20I4 3 DE 20I4 4 DE20I4 17 DE20I4 18 Generator Wattage 20 000 20 0...

Page 5: ...ifications Oil Type See Lubrication section in this manual Oil Capacity 13 5 Quarts Cooling System 50 50 mix DE65F4 MODEL DE65F4 3 DE 65F4 4 DE65F4 17 DE65F4 18 Generator Wattage 55 000 62 000 62 000...

Page 6: ...ont cover of this manual for future reference and for identification whenever requesting field or factory assistance Primary fields needed for assistance are complete model number and serial number EN...

Page 7: ...ting the generator Due to the different designs configurations options weights site conditions and available material handling equipment specific lifting instructions are not provided for each individ...

Page 8: ...mes larger than the radiator face The extra air inlet area is required to minimize restriction and to provide combustion air for the engine Do not block fresh air intakes with other equipment as this...

Page 9: ...start up A customer supplied 12 Volt battery is required to complete the installation Installation of the highest CCA rated battery within the correct BCI group will increase cold weather starting pe...

Page 10: ...make sure that a new battery is fully charged before installing it on a generator set Failure to do so can cause damage to the engine control module in the generator set All connections must be clean...

Page 11: ...r and the load Based on wire type and temperature rating Wire has been derated for 40 C ambient temperature Wire Temperature Rating CB AMP Cu Conductor AI Conductor kW Voltage PH 75 C 90 C 75 C 90 C 2...

Page 12: ...to verify correct installation before starting the engine Engine oil Fill as required with proper grade qty Engine coolant Fill as required with proper mixture Unit mounting base properly bolted down...

Page 13: ...tion Warning alarms are self resetting when the fault condition is removed The icon will appear steady in they display SHUTDOWN Shutdowns are critical alarm conditions that stop the engine and draw th...

Page 14: ...fter the Safety On timer has expired Generator Under Frequency The generator frequency has fallen below the pre set pre alarm setting after the Safety On timer has expired Generator Over Frequency The...

Page 15: ...ng the engine Engine oil Fill as required with proper grade qty Engine coolant Fill as required with proper mixture Unit mounting base properly bolted down Clearance for service and maintenance on all...

Page 16: ...16 OPM 103 REV B KEY START PANEL SCHEMATIC WIRE 91 IS NOT INCLUDED WITH THE DE45 DE90 MODELS CONTROL BOX AC WIRING...

Page 17: ...EMATIC DE20 DE30 ENGINE HARNESS SCHEMATIC 7 7 51 725 0 67 57 5 3 8 3803 8 1 2 35 668 5 6 1 5 22 17 7 03 6 1 5 8 9 6 1 5 2 3 8 6 1 725 2 3 8 6 5 67 57 62 12 2 22 17 127 6 22 17 1 2 35 6685 6 7 67 1 5 6...

Page 18: ...18 OPM 103 REV B 4510 ELECTRIC START PANEL...

Page 19: ...19 OPM 103 REV B THREE PHASE AC WIRE HIGH AND LOW WYE THREE PHASE AC WIRING DELTA SINGLE PHASE 311 WINDING...

Page 20: ...d fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some st...

Reviews: