13
OPM-103
REV B
the allowable level the Safety Latching Relay button will pop out and
the unit will shutdown. You will also get a check engine light at this
time. If you find the unit stopped with the relay button popped out,
it could have been caused by either low oil pressure or high water
temperature.
DSE4510 ENGINE CONTROLLER
STOP/RESET (red button) - This button places the
module into its Stop/Reset mode. This will clear any
alarm conditions for which the triggering criteria have
been removed. The fuel supply de-energizes and the
engine comes to a standstill. Should a remote start
signal be present while operating in this mode, a
remote start WILL NOT occur.
AUTO (white button) - This button places the module
into its Automatic mode. This mode allows the module
to control the function of the generator automatically.
The module will monitor the remote start input
and once a start request is made, the set will be
automatically started and placed on load. The module
will then wait until the next start event.
START (green button) - Pressing this button from
STOP/RESET will start the engine and run the load.
MENU NAVIGATION - Used for navigating the
instrumentation, event log, and configuration screens.
PROTECTIONS
When an alarm is present, the common alarm LED if configures will
illuminate. The LCD display will show an icon to indicate the failure.
WARNINGS
Warnings are non-critical alarm conditions and do not affect the
operation of the generator system, they serve to draw the operator’s
attention to an undisirable condition. Warning alarms are self-resetting
when the fault condition is removed. The icon will appear steady in they
display.
SHUTDOWN
Shutdowns are critical alarm conditions that stop the engine and draw
the operator’s attention to an undesirable condition. Shutdown alarms
are latching. The fault must be removed and the STOP/RESET button
pressed to reset the module. The icon will appear flashing in the
display.
MODULE DISPLAY
FRONT PANEL CONFIGURATION
1. Press the and the buttons together to enter the editor
mode.
2. Press the or navigation buttons to cycle through the front
panel editor to select the required page in the configuration tables.
3. Press the to select the next parameter or to select the
previous parameter within the current page.
4. When viewing the parameter to be edited, press the button,
the value begins to flash.
5. Press the or buttons to adjust the value to the required
setting.
6. Press the button to save the current value, the value ceases
flashing.
7. Press the
button to save and exit the editor, the configuration
icon is removed from the display.
NOTES:
Pressing ans holding the
or
buttons will give auto-repeat
functionality. Values can be changed quickly by holding the
buttons for a prolonged period of time.
The editor automatically exits after 5 minutes of inactivity to
ensure security.
The PIN number is not set by WINCO when the module leaves the
factory. If the code has been ‘lost’ or ‘forgotten’, the module must
be returned to the DSE factory to have the module removed. A
charge will be made for this procedure.
NB - This procedure cannot be performed away from the factory.
The PIN number is automatically reset when the editor is exited
(manually or automatically) to ensure security.
Example of DSE home page display