Wilo WEH Installation And Operating Instructions Manual Download Page 9

WILO SE 02/2014

5

English

tenance work. The installation should be freely 
accessible from at least two sides.
The installation surface must be level and hori-
zontal.

7.2  Hydraulic connection

ATTENTION! Observe the requirements from 

the water supply companies and the local rules 

in force.

• 

Valves must be fitted on the manifolds to isolate 
the pressure-maintaining system if required.

• 

The installation must be fitted with a diaphragm 
pressure tank (Connection Fig. 5).

• 

The existing pipes must be installed free from 
stresses.
Compensators with length limiters for flexible 
connecting pipes are recommended for this pur-
pose in order to avoid stresses on the pipe con-
nections and minimise the transmission of install-
ation vibrations to the building installation.

For the horizontal versions with 1 and 2 pumps

The connection to the tank is done as follows 
(Connection Fig. 5):

• 

Connection of the suction parts to the pumps 
with union nut (within the scope of delivery).

• 

Connection of the suction parts to the tank with 
union nut 1"1/4 (pos. 22).

• 

Connection of the overflow assembly and filter 
to the tank with union nut 1" (pos. 23).

• 

Flexible connection to the pressure-maintaining 
system with gasket (supplied in a plastic bag).

 

- Version 1 pump => connection to the 5 way 

connector.

 

- Version 2 pumps => connection to the mani-

fold.

• 

Connection of the electrovalve 1" to the tank 
(pos. 25) with union ½".

• 

Connection of the float switch (pos. 18) and fil-
ling ( pos. 17) to the tank.

• 

A drain valve 1" (pos. 26 is supplied with the 
module.

• 

An overflow opening 1"1/4 (pos. 27) is available 
and must be connected.

For horizontal version with 2 pumps

The connection of the discharge manifolds can be 
made either on the right or left hand sides of the 
installation. It is recommended to close the ports 
that are not used with threaded caps.

For vertical version with 2 pumps

• 

The connection of the suction and discharge 
manifolds can be made either on the right or left 
hand sides of the installation. It is recommended 
to close the ports that are not used with threa-
ded caps.

• 

A degassing connection (pos. 24 ) is connected 
to the degassing assembly (pos. 28).

7.3  Electrical connection

WARNING! Risk of burn! Electrical shock hazard!

Electrical connections and checks must be per-
formed by an authorised electrician and according 
to the standards in force.

To make the electrical connection, the corres-
ponding installation and operating instructions 

and attached electrical circuit diagrams must be 
observed. General points to be considered are 
listed below:

• 

The type of current and voltage of the mains 
connection must comply with the details on the 
rating plate and the circuit diagram of the swit-
chgear.

• 

The electrical connecting cable must be adequa-
tely dimensioned according to the total power 
of the pressure-maintaining system (see rating 
plate).

• 

As a protection measure, the pressure-main-
taining system must be earthed according to 
the rules (i.e according to the local regulations 
and circumstances). The connections intended 
for this purpose are identified accordingly (see 
circuit diagram).

• 

The base frame has to be connected to earth by 
using an earth braid linked to the frame.

7.4  Float switch

The electrical connection of the switches' float 
level at the terminals of the switchgear is done in 
the factory.
They are installed on the tank:

• 

Float switch against a low water level, for dry run 
protection (pos. 18): 
Place the float running protection in the tank so 
that the system stops when the minimum water 
level is reached, at least 10 cm above the drain 
plug from the pump.

• 

Float filling (pos. 17): 
Place the float filler in the tank so that the sys-
tem meets the water level when filling level is 
reached.

8. Commissioning

We recommend that the pressure-maintaining 
system is first commissioned by the nearest WILO 
customer service agent or ask your central cus-
tomer service department.

8.1  General preparation and checking

• 

Before switching on the system for the first time, 
check if the wiring has been done correctly on 
site, particularly the earthing.

• 

Check if the pipe connections are stress-free.

• 

Fill the installation and check it visually for leaks.

• 

Open the shut-off valves on the pumps and in 
the suction and discharge manifold.

• 

Loosen the pump vent screws and slowly fill the 
pumps with water so that the air can escape 
completely.

ATTENTION! 

Do not allow the pump to run dry. 

Dry running destroys the mechanical seal.

• 

Check the direction of rotation of the pump: 
during a brief start, check whether the direction 
of rotation of the pumps is the arrow on the label 
on the pump. If the rotation is incorrect, interch-
ange two phases.

WARNING! Risk of burn! Electrical shock hazard

!

Switch off the installation's main switch before 
changing the phases.

• 

Check if the motor heat protections inside the 
switchgear are set for the right rated current. See 

Summary of Contents for WEH

Page 1: ...Wilo WEH WEV Pioneering for You 4 158 278 Ed 03 2014 04 Wilo en Installation and operating instructions fr Notice de montage et de mise en service...

Page 2: ...Fig 2a Fig 2b 12 2 8 1 7 17 18 1b 1a 5 9 21 7 8 1 17 18 1b 1a 5 6 9 2 4 21...

Page 3: ...Fig 2c 2 2 21 7 1 18 17 4 8 1a 1b 5 4 8 9...

Page 4: ...Fig 2d 2 1 28 1a 21 4 3 5 1b 6 7 10a 10b 9 8 11...

Page 5: ...Fig 3a Fig 3b Fig 4 Fig 5 15 15 16 14 14 15 16 14 20 19 27 25 24 23 22 26 17 18...

Page 6: ...he product It draws attention to possible problems Information that appears directly on the product such as Direction of rotation arrow Identifiers for connections Name plate Warning sticker must be s...

Page 7: ...lied on a pallet it is protected from moisture and dust with a transparent plastic cover The equipment must be transported by means of authorised load devices ATTENTION The handling should be done by...

Page 8: ...ms are delivered with Float for filling control pos 17 to be mounted on the tank Float switch against a low water level for dry run protection pos 18 to be mounted on the tank A unit with a filling el...

Page 9: ...make the electrical connection the corres ponding installation and operating instructions and attached electrical circuit diagrams must be observed General points to be considered are listed below The...

Page 10: ...the desired opening pressure has been reached To adjust the drain valve of the vessel Turn the button Fig 2a 2b and 2c pos 8 counter clockwise until the pressure starts to drop The discharge valve is...

Page 11: ...the suction strainer does not let air in or the tank filling point is too close from the strainer A pump is obstructed by particles Have the pump dismantled and cleaned Voltage of the motors too low C...

Page 12: ...signal tique les autocollants d avertissement doivent tre imp rativement respect es et main tenues dans un tat bien lisible 2 2 Qualification du personnel Il convient de veiller la qualification du pe...

Page 13: ...plastique transparente Le transport doit tre r alis l aide d un outil de levage de charge d ment autoris ATTENTION La manipulation doit tre effectu e par un personnel qualifi et un mat riel adapt et a...

Page 14: ...14 et vanne d arr t pour version 2 pompes Fig 3a rep 16 est mont au niveau du refoulement Attention en fonctionnement la vanne d arr t rep 16 doit toujours tre en position ouverte De plus tous les sy...

Page 15: ...vient de respecter absolument la notice de montage et de mise en service correspondante ainsi que les sch mas lectriques fournis D une mani re g n rale les points respecter sont les suivants Il n est...

Page 16: ...on dans l ins tallation Rel cher le s commutateur s la pression d ou verture d verseur d sir e Au besoin ajuster avec le robinet vidange de la chaudi re Tourner la molette Fig 2a 2b et 2c rep 8 dans l...

Page 17: ...ier du moteur concern et contr ler l isolement du stator par rapport la terre Remplacer le moteur si n cessaire Manque de pression au refoulement D bit sup rieur aux possibilit s du module Envisager l...

Page 18: ......

Page 19: ...2785961 info wilo kz Korea WILO Pumps Ltd 618 220 Gangseo Busan T 82 51 950 8000 wilo wilo co kr Latvia WILO Baltic SIA 1019 Riga T 371 6714 5229 info wilo lv Lebanon WILO LEBANON SARL Jdeideh 1202 2...

Page 20: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: