Installation and operating instructions Wilo-SiFire System

39

• Check the oil and coolant level of the engine.
• If engines are cooled by water through a radiator 

or heat exchanger, check specific operations 
specified in the instruction manual of the engine. 
To top up the level of fluids, use oil and coolant 
advised by indications given in the instruction 
manuals of diesel engines in annex to this instruc-
tion manual.
Follow the commissioning procedures with help of 
the instruction manual of diesel pump box.

CAUTION! Risk of product damages!
To avoid overheating which could damage the 
main pumps, always check that the water flow 
through the recirculation circuit is fitting with 
requirements of pump technical sheet. If there 
are problems in recirculation circuit or if the 
minimum flow level used to test start and run-
ning of pumps is not guaranteed, open other cir-
cuits (for example, the flow meter, valve for 
testing the tightness of gate valve, drain valve, 
etc).

WARNING! Risk of false reaction of the opera-
tor!
The engine’s accelerator lever is locked. For that 
reason, the engine always starts at max speed!
Allow the pump to run for 20 minutes to check if 
the speed motor is compatible with the indica-
tion on the group label. 

CAUTION! Risk of product damages!
Make sure that none of the following points 
exist. Otherwise, immediately stop the pump 
and remove malfunctioning causes before start-
ing it again (also refer to chapter faults, causes 
and solutions): 

• Rotating parts in contact with fixed parts
• Unusual noises and vibrations
• Loose  bolts
• High temperature on motor housing
• Exhaust gas in the pump room
• Leakage on mechanical seal

Vibrations, noise and excessive temperatures 
could be due to misalignment of motor/pump 
coupling.

8.4.3 Commissioning jockey pump

Manual Start

Follow commissioning instructions with help of 
the manual of jockey pump box.

If the rotation direction is not correct, turn off the 
electrical supply of the box and switch two out 
three positions of phases in the control panel sup-
ply line. Do not invert with the yellow-green earth 
connection wire. 

CAUTION! Risk of malfunction!
For the jockey pump which maintains pressure 
on the installation, make adjustments, for 
example insert a diaphragm or a valve, to ensure 
that even if just one sprinkler is opened, the 
jockey pump does not compensate this.
For adjustments of jockey pumps, see the curves 
of different models of pumps mentioned in the 
catalogue. 

If there are troubles for starting pumps, refer to 
the chapter faults, causes and solutions of the 
jockey pump box and pump instruction manuals.

8.4.4 Filling of installation

If the unit is not filled, use the jockey pump after 
checking that the operations described in previ-
ous chapter have been correctly done.
In that phase, open one or more drain pipes on the 
sprinkler circuit to bleed air from the system.
Start the jockey pump. The system is slowly filling, 
expelling air out of the system. Once water starts 
to flow from drain pipes, close them and wait until 
the predetermined pressure is reached and the 
jockey pump stops. If the pump does not stop, 
check if there are no leaks and check again the 
calibration of the pressure switch which controls 
pump.
Once the unit has reached the set pressure, which 
must be higher than the automatic main pump 
start-up pressure, wait that the pressure remains 
stable before turning the system on automatic 
mode.

Summary of Contents for SiFire

Page 1: ...re EN Pioneering for You 4 188 030 Ed 01 2013 11 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbouw en bedieningsvoors...

Page 2: ...Fig 1 Fig 2a A 2 2 E B C D...

Page 3: ...Fig 2b Fig 3 21 25 26 13 11 12 19 15 22 27 20 24 23 2 1 14 4 16 7 5 6 10 18 17 9 9 10 8 3...

Page 4: ...Fig 4 Fig 5...

Page 5: ...Fig 6a 3 5 D D 4 D 2 3 C min max 1 8 m s Fig 6b min 3 5 D D 4 D max 2 m 2 3 C max 1 8 m s...

Page 6: ...Fig 7 Fig 8 max 3 2 m min A B C D 2 4 5 6 3 8 7 1...

Page 7: ...Fig 9a Fig 9b A B C D 800 800 800...

Page 8: ...Fig 1a Fig 9a variant Fig 9b variant A B C D 800 800 800...

Page 9: ...Fig 10 Fig 11 1 2 1 2 1...

Page 10: ......

Page 11: ...de Einbau und Betriebsanleitung 5 en Installation and operating instructions 29 fr Notice de montage et de mise en service 51 nl Inbouw en bedieningsvoorschriften 75...

Page 12: ...sel pump 16 Connection for priming circuit of main pump 17 Main pump 18 Jockey pump 19 Tank for fuel leakages 20 Fuel tank vent valve 21 Fuel level gauge 22 Drain for cleaning of deposit in fuel tank...

Page 13: ...ructions Wilo SiFire System 27 Fig 9a Variant Exhaust air for combustion and cooling diesel engine Fig 9b A Muffler B Exhaust thermal protection C Condensation drain D Expansion joint Fig 10 Automatic...

Page 14: ...7 Installation and electrical connection 34 7 1 Installation 34 7 2 Safety recommendations 34 7 3 Control and environment 35 7 4 Electrical connection 35 7 4 1 General 35 7 4 2 Hydraulic connection 36...

Page 15: ...t be adhered to but also the special safety instructions with danger symbols included under the following main points 2 1 Danger symbols used in this operating instruction Symbols General danger symbo...

Page 16: ...l installation and maintenance work iscarried out by authorised and qualified personnel who are sufficiently informed from their own detailed study of the operating instructions Work on the product un...

Page 17: ...eproof and ventilated enough with necessary spaces around pumps for movements and regular main tenance Theroommust beinaccordancewiththe EN 12845 standards Airflow for ventilation and for cooling of e...

Page 18: ...requirements trans port handling difficulties particular perform ances etc using the main components described below main normalised back pull out pumps coupled to an electrical motor or diesel engin...

Page 19: ...tion class IP 54 6 3 Function of the product The operational logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for pump starting The jockey pump of pre...

Page 20: ...void access to the system for unauthorised persons The booster is a fire equipment using AUTO MATIC START and MANUAL STOP ONLY For this reason there must have a clearly visible sign in the system room...

Page 21: ...ous tic and vibration levels In order not to transmit tension to the frame get the defects of alignment between theanchorsandthesupport surfacewith metal shims as shown in the figure 4 CAUTION Risk of...

Page 22: ...following points are checked pipes are positioned in such a way as to avoid air accumulation suction pipes between the intake point and the pumping has to be as shortest as possible Its diameter must...

Page 23: ...be performed by qualified people 8 1 General preparations and check Before switching on for the first time check that the wiring has been done correctly particularly the earth connection To make sure...

Page 24: ...and electrical connections indicated in this manual are cor rectly done Make sure the valves at the suction and discharge side of the pump are open Make sure the pump is primed and filled with water C...

Page 25: ...gas in the pump room Leakage on mechanical seal Vibrations noise and excessive temperatures could be due to misalignment of motor pump coupling 8 4 3 Commissioning jockey pump Manual Start Follow com...

Page 26: ...o start the electric pump through the float signal Then follow pump box instructions to check the correct functioning of automatism Pump with diesel engine Before testing make sure that the return cir...

Page 27: ...iesel engine it is advisable to disconnect the positive terminal of battery to prevent undesired start ups DANGER Risk of fatal injury Before changing the engine oil make sure the temperature is below...

Page 28: ...ssure on diesel pump and the cooling circuit water flow CAUTION Risk of malfunction of the pump Always top up fuel and other fluids after per forming the tests 9 3 Test of automatic start of diesel pu...

Page 29: ...hen origi nal spare parts are replaced by other parts with different characteristics 9 5 Residual risks during facility management WARNING Risk of cut Sharp edges orany not protected threaded parts en...

Page 30: ...h Pump in cavita tion Review calculations to suit pump NPSHr Wrong diameter of the suction pipe and valves Pump in cavitation Review calculations to suit pump NPSHr Air inlet in the suction line Make...

Page 31: ...ck and tighten Sliding between fan and motor and between coupling and coupling cover cap etc Guarantee the correct distance and re assemble Foreign parts in motor or pump Dismantle and remove Not alig...

Page 32: ...re Unusual heating too high water oil temperature Pump overload frictions Dismantle and check Coupling out of axis Align correctly Ambient temperature higher than 40 C Ventilate the space Insufficient...

Page 33: ...perations andhandling thefollowingmaterialsmustbesent to centres specialised in the collection and removal of waste Electromechanical and electronic components Electric cables Batteries Strainers Oil...

Page 34: ......

Page 35: ......

Page 36: ...omagnetycznej 2004 108 WE 2004 108 EG pou it harmoniza n normy zejm na stosowanymi normami zharmonizowanymi a w szczeg lno ci viz p edchoz strana patrz poprzednia strona EL TR RO 3 5 7 5 99 CE Uygunlu...

Page 37: ...20 27442100 Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 Ireland WILO Ireland T 353 61 227566 Italy Borromeo Milano T 39 25538351 Kazakhstan WILO Central Asia 050002 Almaty T 7...

Page 38: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: