Installation and operating instructions • Drive for Wilo-Helix2.0-VE / Wilo-Medana CH3-LE • Ed.01/2022-06
53
Double pump
management
Connect double pump
After selecting the menu item "Connect double pump", the Wilo Net address of the double
pump partner must first be set on both pumps to be paired to a double pump. E.g. pump I has
the Wilo Net address 1, pump II has the Wilo Net address 2: Then address 2 must be set in
pump I and address 1 for pump II.
After configuring the partner addresses, the double pump connection can be started or can-
celled by confirming via the menu item "double pumps pairing".
NOTICE
The pump from which the double pump pairing is started is the main
pump. The main pump is to be the pump to which the pressure sensor is
connected.
Connect double pump
Double pump partner
address
Establish double pump
pairing
Double pump
partner address
2
After configuring the partner addresses, the double pump connection can be started or can-
celled by confirming via the menu item "Double pump pairing status".
Establish double
pump pairing
Confirm
(Pump will reset)
Cancel
Double pump connection successful
Twin-head pump
pairing status
Pairing successful
Reset will follow
NOTICE
Different parameters of the pump are fundamentally changed when creat-
ing the double pump function. The pump is then started automatically.
Double pump connection failed
•
Partner not found
•
Partner already paired
•
Partner incompatible