
ENGLISH
11
– Selecting operating mode
The user can choose between four operating modes in menu 1.01:
– Automatic:
Automatic switching between cistern operation
and drinking water backfeed by means of the level
sensor.
– Off:
The pump and the electro valve are not
controlled by the switchgear (dead). The
switchgear continues to function.
– Manual:
This operating mode is available to customer
services. The function of the pump and valve can
be verified via menus 1.02 and 1.03.
– Drinking water:
A continuous supply is provided independently of
the level sensor via the drinking water backfeed
tank.
– Level indicator
The level indicator is suitable for all tank types (plastic, concrete,
metal) and shapes (square and rectangular tanks, upright cylinders,
horizontal cylinders and spheres). The level is displayed as a
percentage of the maximum useful filling volume.
A level sensor with a measuring range of 0 – 5 mWS (0 to 5 metre
water column) is available for the Wilo-RainSystem AF 22. If neces-
sary, the sensor type must be set in menu 2.03 (sensor type).
A water coverage greater than 5 m is not
permitted with a 0 – 5 mWS level sensor!
All data on the tank/cistern geometry required by the level indicator are
set in menus 2.04 – 2.07.
– Menu 2.04 Tank form:
In this menu the geometric form of the
cistern used is set. Specifying the geometric shape of the tank
helps calculate the exact level.
– Menu 2.05 Tank height:
This is where the existing tank height
is set. In the case of horizontal cylinders, the tank height
corresponds to the diameter of the cylinder (see fig. 3).
– Menu 2.06 Height Sensor:
The installation height of the level
sensor above the tank bottom is to be set in this menu. This level
is given as an absolute value in relation to the tank bottom.
WARNING!
– Menu 2.07 Overflow height:
The installation height of the
overflow above the tank bottom is set in this menu. Only the area
between the installation height of the sensor (menu 2.06) and that
of the overflow (menu 2.07) is used to calculate the filling level.
The areas below the sensor and above the overflow cannot be
used by the unit. This level is given as an absolute value in relation
to the tank bottom.
– Function of level control by means of level sensor
(fig. 3)
All level points required for level control are set in menus 2.09 – 2.11.
– Menu 2.09 Backfeed level:
If this level is not reached (menu
2.09) the unit switches to drinking water backfeed mode.
The unit remains in this operating mode until the level “Drinking
water backfeed quantity” (menu 2.10, quantity DW) is exceeded.
The value in menu 2.10 is set as the difference from the level in
menu 2.09. The backfeed level is given as a relative value, i.e. the
reference point is the installation height of the sensor.
In the Drinking water backfeed operating mode the water is taken
from the unit’s drinking water tank. In the standard display this is
represented by the display
> Automatic DW <
in the second line.
– Menu 2.11 Alarm level:
This level monitors the max. filling level in
the cistern. If this level is exceeded, an appropriate alarm signal is
given (4.06 Alarm level error). This signal can only be acknowledged
from a lower level (menu 2.11 – 5 cm Hysteresis). This level is given
as an absolute value in relation to the tank bottom.
The unit automatically switches over to Drinking water mode.
4.2.1 Products delivered
The switchgear (fig. 2) is set and operated in various menus which
appear in the display. The menus are accessed via the control panel
with 3 keys. They have the following functions:
Scroll backwards
Scroll forwards
Confirm key
The green LED indicates that the unit is ready for use.
The following key sequence should be pressed to operate the menu:
Key sequence
è
è
etc.
The main menus appear in the following order
1, 2, 3
1
à
2
à
3
à
4
à
5
à
Select main menu (1, 2 or 3)
1
à
a sub-menu appears, e.g. 1.01 with the
parameters in
>....<
2
à
>....<
becomes
-
....
-
, flashing
3
à
Change to new parameters
4
à
New parameter is saved,
-
....
-
becomes
>....<
5
à
Switch to next sub-menu
When all sub-menus have been completed,
the system returns to the main menu.
Description of programming stages
The individual menus are listed and described in
Table I
.
If no key is pressed on the switchgear for 15 minutes,
the display disappears. The display is re-activated
by pressing
or if an error occurs.
4.2.2 Changing parameters in the switchgear
Only the menu points 1.0x (Operating mode menu) and 2.02
(Language menu) are settable in the delivery state. In all other points it
is not possible to change the parameters. To be able to also change
these points, the parameter change must be released. The correct
procedure for this operation is described below:
WARNING!
– Switch to standard display using the
or
keys.
– Press keys
à
à
in this order with a gap of at least one
second between each one.
After a brief pause the following text appears in the display:
> select operational mode <
.
All parameters can now be changed.
– If no parameters are changed for 3 min., the parameter blocking
function is activated automatically by the unit.
P:4.3bar V:100%
> Automatic rw<
29135_Wilo_RainAF22_GB 26.05.2000 8:23 Uhr Seite 11 (1,1)
Summary of Contents for AF 22
Page 4: ...Bild 4 Elektrischer Anschlu 29135_Wilo_RainAF22_Titel 26 05 2000 7 16 Uhr Seite 4 1 1...
Page 6: ...Bild 7 Bohrskizze 29135_Wilo_RainAF22_Titel 26 05 2000 7 17 Uhr Seite 6 1 1...
Page 25: ...ENGLISH 19 Fig 4 Electrical connection 29135_Wilo_RainAF22_GB 26 05 2000 8 24 Uhr Seite 19 1 1...
Page 27: ...ENGLISH 21 Fig 7 Drilling diagram 29135_Wilo_RainAF22_GB 26 05 2000 8 25 Uhr Seite 21 1 1...
Page 39: ...FRAN AIS 33 Fig 7 Sch ma d al sage 29135_Wilo_RainAF22_F 26 05 2000 8 39 Uhr Seite 33 1 1...