Use this table to identify and remedy a problem or fault:
Problem
Cause
Action
.
The unit does not start
No power input
Check that the power cable
.
Display not switched on
is correctly connected to
power source and unit
If the power cable is
connected, check the
branch fuse
.
Unit does not work
Hygrostat has sensored a
Reduce preset value of the
.
Green control lamp does
relative humidity which is below hygrostat or change to
not illuminate
the preset value and has shut
manual operation
.
HYG STOP
shown on
off the unit to save energy
Refer the chapter about
the display
use of built-in hygrostat on
page 9
.
Yellow control lamp
The water tank is full or pump
Empty the water tank or
illuminates
(accessory) blocks
eleminate pump
Display shows
FULL
blockade
.
Red control lamp
Fault which results in
Refer table of manual
illuminates
operation interruption
on page 12 about
fault reports
.
Dehumidifier operates
Time for service interval
Maintain the dehumidifier
.
Green control lamp
is run off
as described in the
illuminates
chapter about the service
.
SERVICE
flashes in
interval counter
display
.
Dehumidifier operates
RH%-Sensor defective
Replace RH%-Sensor
.
When RH% is activated,
the display shows
SENSOR FAIL
.
kW/h and operating
Data-store-battery empty
Exchange battery
hour are not on display
refer page 11
without main power
supply
22 of 33
Fault finding and solving
Summary of Contents for 3100430
Page 1: ...Perfection is our aim Manual Dehumidifiers KT 330 KT 430 KT 830...
Page 17: ...16 of 33 Checklist User...
Page 18: ...17 of 33 Checklist User...
Page 19: ...18 of 33 Checklist User...
Page 20: ...19 of 33 Checklist User...
Page 29: ...28 of 33 Exploded View KT 330...
Page 31: ...30 of 33 Exploded View KT 430...
Page 33: ...32 of 33 Exploded View KT 830...