18
Install the ceramics into the appliance according to these instrucons—see pages 24 through to 27.
Refit the glass panel and front trim cover—See page 17
Test the operang pressure of the appliance by aaching a pressure gauge to the test point of the appliance. This connecon
should take place when the appliance is OFF. Ensure that gas is turned on at the gas meter and purge the air from the
appliance. To light the appliance follow the instrucons below:
Slide the control lever fully to the (IGN) posion and hold. The spark generator should spark connuously, ensure the
spark is being generated correctly at the pilot assembly. Connue with this procedure unl the air is purged from the
appliance and the pilot and main burner are lit. Once lit hold the lever pushed to the le for up to a further 10-15 seconds.
Once the pilot is established and secure release the lever—this is now the (LOW) posion. Now slide the lever to the right
to the (HIGH) posion. Allow the appliance to run for a minimum period of 5 minutes. Next check that the inlet pressure to
the appliance is 20 mbar ±1 mbar. Move the lever to the right against the spring pressure to the posion to turn OFF.
When lighng this appliance it should be noted that the main burner will light at low rate during the pilot ignion process.
To check for sasfactory clearance of products of
combuson, close all doors and windows and leave the
appliance burning on HIGH for five minutes.
Insert a lit smoke match into the match holder supplied,
poinng the match to the right as shown.
Push the holder and match into the centre slot at the top
of the appliance. Once fully in, the holder should be
rotated 90 degrees
Now move the match holder to the le side of the slot
AS FAR AS POSSIBLE
. This will posion the smoke match
at the internal dra diverter.
If some smoke appears at the convecon outlet it may
be the smoke match is not close enough to the diverter.
Move the holder slightly to the right and rotate the
holder a lile further clockwise.
DO NOT MOVE MATCH HOLDER FROM THIS POSITION
UNTIL THE SPILLAGE CHECK IS COMPLETE.
SPILLAGE TEST
Check the clearance of combuson products. It is important to note that a special match holder is provided with
this appliance. Do not remove this item from the property aer installaon is complete—it will be required for
future inspecons. If this part is lost contact the manufacturer immediately to purchase a replacement.
All the smoke must be drawn into the flue. If spillage occurs allow a further 5 minutes and repeat the test. If spillage sll occurs
turn off the appliance and seek expert advice. If an extractor fan is situated in the room the spillage test should be repeated
with the fan running. If there is a connecng room with an extractor fan the test should be repeated with all the doors to that
room open and the extractor fan running.
This appliance is fied with an atmospheric sensing system in the form of an oxygen sensing pilot burner. This is designed to
shut the fire off in the event of products being spilled into the room where the fire is being operated. It is important to note
that this spillage monitoring device should not be disabled or be adjusted by the installer. If the spillage monitoring device
(O.D.S pilot) is replaced it must only be exchanged with a suitable component which is supplied by the manufacturer.
1
2
3