Technical data
Wieland Electric GmbH | BA000966 | 08/2017 [8151]
88
SP-COP1 / SP-COP-xxx
Test outputs (T1 - T4)
Number of outputs
4 (with 4 test signal generators)
Type of output
Semiconductor, push-pull, short-circuit-proof
Output voltage HIGH
U
A1
- 1.2 V
Output current LOW
-10 mA (limited)
Output current HIGH
Single output: max. 120 mA
Total of all test outputs: max. 120 mA
Test pulse rate (test period)
1 to 25 Hz, configurable
Test pulse duration (test gap)
1 to 100 ms, configurable
Load capacity
1 µF for test gap
≥
4 ms
0.22 µF for test gap 1 ms
Line resistance
< 100
Ω
Safety outputs
SP-COP1: Q1 … Q4 / SP-COP2-ENx: Q1 to Q4, IQ1 - IQ4
Number of outputs
• SP-COP1:
• SP-COP2-ENx
4
8 (4 fixed and 4 selectable outputs)
Type of output
High-side MOSFET, short-circuit-proof and current-
monitored
Output voltage HIGH
U
Qn
≥
U
Bx
- 0.6 V
Output current HIGH
Max. overload current/duration
≤
4.0 A
≤
12 A / 8 ms
Total current I
tot
T
U
≤
45°C
T
U
≤
55 °C
T
U
≤
65 °C
Per output pair (Q1/2, Q3/4, IQ1/2, IQ3/4)
≤
4.0 A
≤
2.5 A
≤
1.6 A
Output test, can be deactivated
3,4,5
Test pulse width
Test pulse rate
≤
450 µs
10 Hz
Leakage current LOW
6
< 0.1 mA
Load capacity
0.5 µF
Line resistance
7
< 200
Ω
Maximum permissible coil energy
without external protection ele-
ments
8
< 0.125 J
Response time
Depends on logic setup
(Details:
System response times [ch. 12.1, p. 81]
1
For detailed information regarding the safety configuration of your machine/system, please
contact the Wieland Electric branch in charge of your area.
2
Do not connect any other safe inputs in parallel when the reverse current could lead to a
HIGH state at the other input.
3
When activated; in that case, the outputs are tested regularly (brief LOW switching). When
selecting the downstream control elements, make sure that the test pulses will not cause
switch-off with the previously listed parameters or deactivate the test pulses at the outputs.
4
When safety outputs are being used without test pulses, then either all of the safety outputs
without test pulses must be switched off at least once a year simultaneously for at least one
second or the samosPRO system must be restarted by switching off the supply voltage.
Summary of Contents for samos PRO COMPACT
Page 1: ...samos PRO samos PRO COMPACT Hardware Manual Doc no BA000966 Last Update 08 2017 8151...
Page 103: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 103 Declaration of Conformity Page 2...
Page 104: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 104 Declaration of Conformity Page 3...
Page 105: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 105 Declaration of Conformity Page 4...