Error No.
Error type Logbook message
System behavior
Remedy
10100012
Error
The controller could not respond
positively to the request.
Remains connected Repeat
support request
10100013
Error
The maximum number of repeated
requests is exceeded.
Separate connection Repeat
support request
10100015
Error
Connection cannot be set up to the
controller.
No connection
Check connection
support request
10100016
Error
The password for the user to be
logged on is invalid.
Remains connected Check password
10100017
Error
The controller could not adopt the
desired state.
Remains connected Repeat
support request
10100018
Error
The station's memory card is not
inserted.
Separate connection Insert valid SD card
10200002
Error
The project on the control is invalid. No connection
Transfer a new valid
project
10200003
Error
The verification status of the project
and controller are different.
No connection
Reverify the project
10200004
Error
The PC project and the project on
the controller could not be synchro-
nized.
No connection
Disconnect and
reconnect
support request
10200005
Error
The current user does not have au-
thorization to communicate with the
controller.
Connection was disconnected.
No connection
Redefine the user
rights
10200006
Warning
The project on the controller does
not match the module configuration.
Remains connected Adjust hardware or
project
10200007
Error
The controller reports an error.
-
Support request
10200008
Error
The controller reports a deviating
CRC in the project file.
-
Repeat of
Support request
work step
10200009
Error
The permissible waiting time for the
operation was exceeded.
-
Repeat
support request
1020000A
Info
The verification has been interrup-
ted.
-
Repeat
support request
1020000B
Warning
The faulty project file is still in the
station and must be replaced by the
updated project file.
Please reconnect and load the up-
dated project on the station.
-
Update the device
with the repaired
project
10300001
Error
The data of the logic analyzer could
not be saved.
-
Check Windows user
rights
10300002
Error
The data of the logic analyzer could
not be loaded.
-
Repeat
support request
10300003
Error
Input/output was not found.
-
Support request
10400001
Error
The log messages could not be sa-
ved.
-
Check Windows user
rights
10400002
Error
The file contains more than 64 log
messages. Only the first 64 were
imported.
-
Reduce the number
of log messages
10400003
Error
The log messages could not be im-
ported.
-
Support request
10500001
Error
The logon on the controller was
faulty.
-
Repeat
support request
Summary of Contents for samos PRO COMPACT
Page 1: ...samos PRO samos PRO COMPACT Hardware Manual Doc no BA000966 Last Update 08 2017 8151...
Page 103: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 103 Declaration of Conformity Page 2...
Page 104: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 104 Declaration of Conformity Page 3...
Page 105: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 105 Declaration of Conformity Page 4...