Product description
Wieland Electric GmbH | BA000966 | 08/2017 [8151]
32
SP-SDIO input/output expansion module
888376459
Description
888377995
The SP-SDIO module is an input/output expansion with eight safe inputs and four safe outputs.
It has two test signal generators: one for test output X1 and one for test output X2.
The SP-SDIO module offers the following functions:
• Monitoring of connected safety devices
Connecting devices [ch. 4, p. 43]
• Forwarding of input information to the controller module
• Receipt of control signals from the controller module and corresponding switching of out-
puts
• Fast shut-off: Direct switch-off of the actuators connected on the module. This results in a
significant reduction in the response time of the entire system. Only 8 ms are needed in
the response times of the devices at the inputs and outputs in order to switch-off the out-
puts. The runtimes on the internal safety bus and the Logic Execution Time do not play any
role in this case.
System response times [ch. 12.1, p. 81]
• Activating or deactivating test pulses at the outputs (Q1–Q4) with firmware version V2.00.0
and higher.
The SP-SDIO module cannot be operated alone; it always requires an SP-COP controller modu-
le (see "samosPLAN
6" programming software).
It is possible to use multiple SP-SDIO84 modules simultaneously (see
). The voltage of the internal logic and the test outputs is supplied via the system connector
and the internal safety bus. The voltage of the Q1–Q4 outputs of the SP-SDIO must be supplied
directly via A1/A2 at the respective module.
ATTENTION
Limited short-circuit detection in the input circuits
• One SP-SDIO module has two test signal generators, X1 and X2.
• Short-circuits between test signal generators of a SP-SDI or SP-SDIO module are detec-
ted. Between different modules the short circuit detection is then only ensured if the test
gaps of the test signal generators are < 4 ms and the test periods
≥
200 ms. Short-circuits
past 24 V DC (after High) at inputs that are connected to test outputs are detected inde-
pendently of the length of the test gaps.
Take note of this during wiring (e.g. by using separate routing or protected lines)!
NOTICE
• The LEDs of inputs I1 to I8 indicate the state of the inputs at an update interval of about
64 ms.
3.8
3.8.1
Summary of Contents for samos PRO COMPACT
Page 1: ...samos PRO samos PRO COMPACT Hardware Manual Doc no BA000966 Last Update 08 2017 8151...
Page 103: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 103 Declaration of Conformity Page 2...
Page 104: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 104 Declaration of Conformity Page 3...
Page 105: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 105 Declaration of Conformity Page 4...