Basic principles, overview and ordering information
© 2002 Wieland Electric GmbH Version 2.4* (December 2002)
Part no. 05.591.3389.0
© 2002 Wieland Electric GmbH
97
Once the maximum value has been achieved, counting continues with the
minimum value. Once the minimum value has been reached, counting continues
with the maximum value.
Counting frequency:
up to 200 kHz
Counter width:
32 bit
Counting range:
-2
31
to 2
31
-1
Edge evaluation:
4 fold
Setting via PLC:
Operating mode, direction for reference movement, speed for reference
movement, use of N for reference movement, selection of outputs, deletion of
counter, inverted counting direction, inverted direction of travel for outputs,
inverted speed for outputs, count value, pre-disconnection value, disconnection
value, overwrite for inputs/outputs.
Setting via bus coupler:
Overwrite inputs/outputs with FORCE/LOCK.
Data storage:
Storage of data or configuration is not implemented in the event of voltage failure.
Signal level DC 24 V for input and output signals.
Inputs: TRACK A, B and N, END+, END-
Outputs:
DIR+, DIR-, SPEED
Can be switched to: DIRECTION, TRAVERSE, SPEED
Operating modes
Reference movement, variant 1 (feed movement)
Fast (default; can be switched to slow) in direction for reference movement until
END+ or END- is active. Then slow in opposite direction until N is active. Delete
counter and OFF.
Reference movement, variant 2 (feed movement)
Fast (can be switched to slow) in direction for reference movement until END+ or
END- is active. Then slow in opposite direction until limit switch is no longer active.
Delete counter and OFF.
Reference movement, variant 3 (band movement)
Fast (can be switched to slow) in direction for reference movement. After END+ to
24 V (i.e. alternative use of this limit switch) until N is active. Delete counter and
OFF. The end of the reference movement is signalled by the PLC.
Positioning movement:
Fast until pre-disconnection value, slow until disconnection value and then OFF.
The end of the positioning movement is signalled by the PLC.