2.20.6 Optional functions of
ricos
COUNTER
The optional functions can be activated via the control data. The functions are
available for each counter.
The functions of the input terminals COUNT- can be modified:
1. Deletion of counter content (DELETE)
2. Selection of counting direction (DIRECTION)
Threshold comparison with rapid output signals (ON delay approx. 0.02 ms, OFF
delay approx. 0.2 ms).
Two variants for comparison of threshold value:
1. Count < threshold value
2. Count >= threshold value
When using the module for 2 x 32 bit counters, 2 threshold values can be
preselected.
Interference suppression with digital filters for
200 Hz, 2 kHz, 20 kHz, 200 kHz.
2.20.7 Complete control data from PLC to module (outputs)
5 words are transmitted from the PLC to the module. The first 4 words have
various meanings depending on word 5.
4 x 16 bit counters (Word 5, Bit 11 = 0)
Word 1
Word 2
Word 3*
Word 4*
Word 5
X X X
X
0000 0000 xxxx xxxx
b
No effect i.e. no data
is loaded into the
module
Count of counter
1
X
X
X
xxx1 0000 xxxx xxxx
b
Load counter 1
X
Count of counter
2
X
X
xx1x 0000 xxxx xxxx
b
Load counter 2
X X Count of counter
3
X
x1xx 0000 xxxx xxxx
b
Load counter 3
X X X
Count of counter
4
1xxx 0000 xxxx xxxx
b
Load counter 4
Count of counter
1
Count of counter
2
Count of counter
3
Count of counter
4
1111 0000 xxxx xxxx
b
Load counters 1 to 4
Threshold 1 of
counter 1
Threshold 1 of
counter 2
Threshold 1 of
counter 3
Threshold 1 of
counter 4
xxxx 0001 xxxx xxxx
b
Load threshold 1
(counters 1 to 4)
Overwrite data of
counter 1 *
Overwrite data of
counter 2 *
Overwrite data of
counter 3 *
Overwrite data of
counter 4 *
xxxx 0011 xxxx xxxx
b
Load overwrite data
(counters 1 to 4
Configuration
data of counter 1
*
Configuration
data of counter 2
*
Configuration
data of counter 3
*
Configuration
data of counter 4
*
xxxx 0100 xxxx xxxx
b
Load configuration
data (counters 1 to 4)
X: Any word value
x: Any bit value
MSB: Most Significant Byte
b: Binary display *: See below for details
LSB: Least Significant Byte
*Word 3 and word 4 are not transmitted at a set data width of 3. Word 5 is then
transmitted as word 3.