Part no. 05.591.3389.0 © 2002 Wieland Electric GmbH
2.4.3 Technical data of
ricos
4 I AC 115V
ricos
4 I AC 115V
Part no.
83.035.5000.1
Module identifier
24d / 18h
Number of inputs
4
External supply voltage
none
Power consumption of external 24 V power
supply
none
Power consumption of internal 5 V power
supply
0.2 W
Inputs
Switching level
HIGH level AC 74 up to 132 V
LOW level AC 0 up to 20 V
Input current
min. HIGH level (AC 74 V)
≥
5 mA
max. LOW level (AC 20 V)
≥
2.3 mA
Electrical isolation to internal bus
Yes, separately for each channel using optocouplers
See also “General technical data” on page 107.