Basic principles, overview and ordering information
© 2002 Wieland Electric GmbH Version 2.4* (December 2002)
Part no. 05.591.3389.0
© 2002 Wieland Electric GmbH
27
2.5.3 Technical data of
ricos
4 I AC 230V
ricos
4 I AC 230V
Part no.
83.035.5005.1
Module identifier
25d /19h
Number of inputs
4
External supply voltage
none
Power consumption of external 24 V power
supply
none
Power consumption of internal 5 V power
supply
0.2 W
Inputs
Switching level
HIGH level AC 159 up to 253 V
LOW level AC 0 up to 40 V
Input current
min. HIGH level (AC 159 V)
≥
5 mA
max. LOW level (AC 40 V)
≥
2.3 mA
Electrical isolation to internal bus
Yes, separately for each channel using optocouplers