Basic principles, overview and ordering information
© 2002 Wieland Electric GmbH Version 2.4* (December 2002)
Part no. 05.591.3389.0
© 2002 Wieland Electric GmbH
39
2.9.3 Technical data of
ricos
8 I, 8 I/O
ricos
8I, 8I/O
Part no.
ricos
8I, 8I/O
ricos
8I, 8I/O
83.035.3300.0
83.035.3300.1
(with locating clips for equipotential
distribution board)
Module identifier
4
Number of inputs/outputs
8 inputs and 8 combined I/Os, can be used individually as inputs
or outputs
External supply voltage
DC 24 V ± 20% max. 5% residual ripple
Power consumption of external
24 V power supply
0.25 W (without input currents / load currents)
Power consumption of internal
5 V power supply
0.325 W
Inputs
Switching level
HIGH level +15 V up to +30 V
LOW level -30 V up to +5 V
Input current
min. HIGH level (+15 V), I >= 2.5 mA / 3.6 mA*
max. LOW level (+5 V), I <= 0.7 mA / 1.2 mA*
typically (+24 V), I = 4.5 mA / 6.1 mA*
*for combined I/O
Electrical isolation to internal bus
Yes, separately for each channel using optocouplers
Signal delay
<100 µs (hardware)
See also section “Reaction times”
Outputs
Max. output current per output
1 A
Overcurrent and short-circuit protection, parallel operation
possible in groups
(2 groups: 0-3, 4-7)
Max. total current of module
8 A
Switching level
HIGH level = supply voltage – 0.5 V
LOW level <= 1 V
Electrical isolation to internal bus
Yes, separately for each channel using optocouplers
Concurrence
100%
Free-wheeling diode
Integrated
Signal delay
<100 µs (hardware)
See also section “Reaction times”
See also “General technical data” on page 107.
IMPORTANT
Each of the 8 combined I/O channels can either be operated as an input or an
output. This means that both an input address space and an output address
space are reserved in the bus coupler as a process image. The user must note
that an input channel (e.g. initiator) cannot be used simultaneously as an output
channel but that an output can be read back as an input. The switching function
can therefore be monitored by the PLC.
NOTE
In the case of modules with digital combined channels, it should be noted that it is not permitted to
apply 24 V to a combined channel without providing the supply voltage.
Otherwise, the voltage is fed back via the output circuit of the combined channel into the supply
voltage terminal of the module. This can lead to a malfunction or the destruction of the output circuit.