Page 28 | 1-800-343-9463
MPS
031413
Energy
Reduction
(ER)
1. The ER feature can be used to save energy and aids in extending the life of the system.
2. The ER button is located at the top L/H side of the control. The ER feature is activated by pressing
the ER button one time, and the ER logo will appear on the digital display.
3. The purpose of the ER feature is to reduce energy cost, by shifting the Set Point up by 4 degrees,
which will allow the cooling system to run for shorter periods of time, resulting in a reduction in
energy cost.
4. The ER feature allows for Energy Savings at any time - During periods of high ambient tempera-
tures, vacations or business travel.
“Customer Preference Select Mode” (CPSM). See Customer Preference Select Mode Instructions.
Note:
This feature is not available on the Remote Key Pad application.
Set
Button
1. Press the “Set” button once and it will display the Set Point. After approximately 5 seconds, the
display will return to normal operation and display the Bottle Probe temperature.
2. Press and hold the “Set” button for 3-5 seconds until the set point is displayed and the °F symbol
starts blinking. Next press the “UP or Down” arrows to change the Set Point. Next press the “Set”
Point setting.
3. Press and hold the “Set” button during the display of the Hi/Low “Temperature Data History” (hold
from the current time and temperature.
4. Press the “Set” and the “Down Arrow” buttons simultaneously, for 3-5 seconds, and you will access
the “Customer Preference Selection Mode” (CPSM). The CPSM allows the customer to “Fine Tune” the
Control Operating System to their applicable choice.
CPSM Mode
Press the “Set” and the “Down Arrow” buttons simultaneously, for 3-5 seconds, and you will access
the “Customer Preference Selection Mode” (CPSM). The CPSM allows the customer to “Fine Tune” the
Control Operating System to their applicable choice.
The following CPSM options are available for adjustment:
Fon – Humidity Management Enhancement: This parameter is normally set at 5, which should pro-
vide adequate relative humidity for the cellar.
•
An increase in this parameter will increase the Humidity Enhancement (%RH), and a decrease in
the parameter will decrease Humidity Enhancement (%RH).
•
Adjustments should be made in increments of 5, with a maximum of 15, and a minimum of 0.
•
After any adjustment to Humidity Enhancement, you should wait a minimum of three days
to the new setting.
Fof - Humidity Management Enhancement: This parameter is normally set at 1. This parameter
should not be adjusted, as it simply provides an OFF cycle time for the fan, during the compressor
OFF cycle. However, the parameter is located within the CPSM as a convenience to the customer,
should it need to be adjusted.